Omron CS1W-SLK11-21 - 06-2004 Manual page 133

Sysmac link units
Table of Contents

Advertisement

FINS Commands for SYSMAC LINK Units
Response Block
Parameters
Note
116
06
02
31 bytes
Command
Response
Network
code
code
member data
Network member data (response): Four bits are allocated to each node
address to provide information on the status of nodes in the network as shown
below. The function of each of the 4 bits is shown in the diagram following the
table.
Byte
Byte 1
Node address 2
Byte 2
Node address 4
Byte 3
Node address 6
Byte 31
Node address 62
3/7 2/6 1/5 0/4
Bit
0
*Bit 1/5 is used to indicate why the node is not in the network when bit 0/4 is
OFF.
Communications cycle time (response): The actual communications cycle
time is provided here in 4-digit hexadecimal in increments of 100 µ s.
Node address of current polling node (response): The node address of
the Unit that currently is the polling node.
Cyclic operation (response): Indicates the current status of cyclic operation,
as follows:
00: Stopped
01: Active
Cyclic transmission status (response): Indicates the current status of
cyclic transmission, as follows:
00: No transmission
01: Transmission
Communications
cycle time
Node address of
current polling node
Cyclic operation
Bits 4 to 7
Bits 0 to 3
Node address 1
Node address 3
Node address 5
Node address 61
1: In network (0: Not in network)
1: Exited because of an error.* (0: Normal exit)
1: Unit does not respond to polling.
Section 6-4
8 bytes
62 bytes
Cyclic error
Cyclic
counters
non-fatal errors
Cyclic
transmission status