The CPU Bus Unit Area of the SYSMAC LINK Unit is allocated in the PLC's memory (bit area) according to the
unit number as follows (25 words are allocated per Unit):
Unit No.
0
CIO 1500 to CIO 1524
1
CIO 1525 to CIO 1549
2
CIO 1550 to CIO 1574
3
CIO 1575 to CIO 1599
4
CIO 1600 to CIO 1624
5
CIO 1625 to CIO 1649
6
CIO 1650 to CIO 1674
7
CIO 1675 to CIO 1699
Configuration of CPU Bus Unit Area
The configuration of the CPU Bus Unit Area of the SYSMAC LINK Unit is as follows:
Appendix D

CPU Bus Unit Area Allocations

Words
Word
+0
System reserved
+1
Error data
+2
to
Network status
+7
+8
to
Data link status
+23
+24
Power supply status (CS1W-SLK11 only)
Unit No.
8
CIO 1700 to CIO 1724
9
CIO 1725 to CIO 1749
10
CIO 1750 to CIO 1774
11
CIO 1775 to CIO 1799
12
CIO 1800 to CIO 1824
13
CIO 1825 to CIO 1849
14
CIO 1850 to CIO 1874
15
CIO 1875 to CIO 1899
(1 word)
(1 word)
(6 words)
(16 words)
(1 word)