Omron CS1W-SLK11-21 - 06-2004 Manual page 93

Sysmac link units
Table of Contents

Advertisement

CX-Programmer Procedures
Area 1
Node 1
Area 2
Node 1
1,2,3...
76
• The send area sizes will be the same for all nodes participating in the data
links.
• The send node order will be in the order of node addresses
• There will be no nodes that do not receive.
Setting Example
The following example shows the Data Link Table Engineer settings.
Send (1)
Receive
(2)
Receive
(3)
Send (1)
Receive
(2)
Receive
(3)
1. Select Table and then Data Link Engineer. The Data Link Table Engineer
dialog box will be displayed, as shown below.
2. Make the following settings.
• In the Valid Nodes Field, enter the node addresses for the automatic
settings.
• In the Common Link Parameters Field, set the send size for each node
in the CIO Area and in the DM Area. All nodes must have the same
send sizes.
• Set the PLC type in the PLC Type Field under Refresh Parameters. Se-
lect "CV/CVM1."
• In the Start Channel Field, set the first words in the CIO Area and DM
Area data links.
Node 2
Receive
(1)
Send (2)
Receive
(3)
Node 2
Receive
(1)
Send (2)
Receive
(3)
Section 4-12
Node 3
Receive
(1)
Receive
(2)
Send (3)
Node 3
Receive
(1)
Receive
(2)
Send (3)