Ua" Communication Error Between Outdoor Unit And Indoor Unit - Daikin ALTHERMA HT Service Manual

Hide thumbs Also See for ALTHERMA HT:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.61 "UA " Communication Error between Outdoor Unit and
Indoor Unit
UA
Remote Control
UA
Display
UA
AII indoor unit models
Applicable
All outdoor unit models
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
 Excess of connected indoor units
Supposed
 Defect of outdoor unit PC board (A1P)
Causes
 Mismatching of the type of indoor and outdoor unit.
 Setting of outdoor PC board was not conducted after replacing to spare parts PC board.
Troubleshooting
206
subcode 13
subcode 39
Be sure to turn off power switch before connect or disconnect
connector, or parts damage may be occured.
Caution
Is the
outdoor PC board
replaced to spare parts
PC board?
NO
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
Does a
malfunction
occur?
YES
Does the type
of indoor and outdoor unit
match?
YES
YES
NO
NO
ESIE09-08B
The outdoor PC board replaced is
wrong, check PC board type.
Normal
Matches the type of indoor and
outdoor unit.
Replace outdoor unit PC board
(A1P).
(V3169)