SiUS341802E

4. Capacity Range

4.1

Combination Ratio

RXLQ-TATJU, RXLQ-TAYDU, RXLQ-TAYCU
Double outdoor units
Notes: ∗1. If the operational capacity of indoor units is more than 130%, low airflow operation is
RXYQ-TAYCU
Double outdoor units
Notes: ∗1. RXYQ72TAYCU: 70%
General Information
Total capacity index of the indoor units

Combination ratio =

Capacity index of the outdoor units
Min.
Type
combination
ratio
Single outdoor units
70%
enforced in all the indoor units. Refer to page 129 for detail.
∗2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units. And the connection ratio must not
exceed 100%.
∗3. It is permitted to use a maximum connection ratio of 130% in some circumstances – please
contact your local Daikin representative for further details.
Min.
Type
combination
ratio
Single outdoor units
50% ∗1
Triple outdoor units
∗2. If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units. Refer to page 129 for detail.
∗3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected,
the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not
exceed 30% of the capacity index of the outdoor units. And the connection ratio must not
exceed 100%.
∗4. It is permitted to use a maximum connection ratio of 130% in some circumstances – please
contact your local Daikin representative for further details.
Max. combination ratio
Types of connected indoor units
When using
When using at
only FXDQ-M,
least one
When using
FXSQ07-54TA,
FXFQ07/09,
other indoor
FXMQ-PB,
FXZQ05TA,
unit models
FXAQ-P
FXSQ05TA
180% ∗1
200% ∗1
200% ∗1
160% ∗1
160% ∗1
Max. combination ratio
Types of connected indoor units
When using
When using at
only FXDQ-M,
least one
When using
FXSQ07-54TA,
FXFQ07/09,
other indoor
FXMQ-PB,
FXZQ05TA,
unit models
FXAQ-P
FXSQ05TA
180% ∗2
200% ∗2
200% ∗2
160% ∗2
160% ∗2
130% ∗2
Type of connected air treatment
equipments
FXMQ-MF
When FXMQ-MF
is only connected
100%
Type of connected air treatment
equipments
FXMQ-MF
When FXMQ-MF
is only connected
100%
130%

Capacity Range

When FXMQ-MF
and indoor units
are connected
100% ∗2 ∗3
When FXMQ-MF
and indoor units
are connected
100% ∗3 ∗4
8