Siemens SIMATIC IPC RW-545A Operating Instructions Manual page 142

Industrial pc workstation
Table of Contents

Advertisement

Technical specifications
9.2 General technical specifications
Frequency of the supply voltage
Transient voltage interruption
Power consumption
Power loss, heat emission
142
Power supply unit 850 W:
Continuous current at 100 V: ≤ 12 A
Continuous current at 230 V: ≤ 6 A
at startup ≤ 180 A for 3.6 ms
Power supply unit 700 W (2 modules, each 700 W, redundant):
Continuous current at 100 V: ≤ 10 A
Continuous current at 230 V: ≤ 5 A
At startup ≤ 80 A for 3.6 ms for each module
Information on the dimensioning of fuses in higher-level system circuits
A fuse that is designed for the following tripping current is integrated in the power
supply unit of the IPC.
Typical 8 A (for power supply unit 550 W)
Typical 12 A (for power supply unit 850 W)
Typical 10 A (for redundant power supply unit 700 W).
The pulse currents during startup are also taken into account by the "time lag" type. In
the case of a fault, this fuse ensures the correct disconnection of the device from the
power supply system.
If you connect additional devices to the higher-level power supply circuit, use the
following fuses:
> 8 A (for power supply unit 550 W).
> 12 A (for power supply unit 850 W).
> 10 A (for redundant power supply unit 700 W).
The tripping characteristic of the higher-level protection must take into account the
starting currents of both the IPC and the other devices.
50 to 60 Hz, min. 47 Hz to max. 63 Hz, sinusoidal
Power supply unit 550 W:
20 ms for 300 W
≤ 10 events/h; recovery time ≥ 1 s
Power supply unit 850 W:
20 ms for 460 W
≤ 10 events/h; recovery time ≥ 1 s
Power supply unit 700 W (2 modules, each 700 W, redundant):
20 ms for 300 W
≤ 10 events/h; recovery time ≥ 1 s
Power supply unit 550 W, with maximum configuration and 300 W secondary:
≤ 260 W; with 90% efficiency
Power supply unit 850 W,
with maximum configuration and 460 W secondary:
≤ 600 W with 87% efficiency
Power supply unit 700 W (2 modules, each 700 W, redundant),
with maximum configuration and 300 W secondary:
≤ 270 W with 85% efficiency
Power supply unit 550 W:
300 W = 300 J/s = 0.28 BTU/s
Workstation SIMATIC IPC RW-545A Operating
Instructions, 08/2023, A5E52943278-AA

Advertisement

Table of Contents
loading

Table of Contents