Supervision of task operation (RUN error)
10.2.8
Tasks are monitored every two minutes in IED. The message will be screened when a task
stops. If the task is idling, the supervisor monitors the task every 15 minutes.
Error level
(i)
The error level has been set at level 1 (Serious error) unconditionally.
Error message
(ii)
When detecting an error, the error message will be shown on the LCD. LED will be lit up.
Table 10.2-15 Error messages provided by the supervisor in MNT_LOGIC
Message and level
CP1M(RUN) error
Error level
Table 10.2-16 Detailed information in Hexadecimal in MNT_LOGIC
Display
area
10000000: Supervision function itself
Top
20000000: Idle task (1)
row
40000000: Idle task (2)
WW XX YY ZZ
Middle
WW:
FB index in PCM (2)
XX:
FB index in PCM(1)
row
YY:
FB index in SSP3(2)
YY:
FB index in SSP3(1)
WW XX YY ZZ
Bottom
WW:
FB index in CONVSET
XX:
FB index in NMT
row
YY:
FB index in 200MS(2)
YY:
FB index in 200MS(1)
Meaning of the information
Detection of the stopped task in the IED
Serious error (Level 1)
Meaning of the detailed information
Left column
- 809 -
Right column
WW XX YY ZZ
WW:
FB index in SSP2(2)
XX:
FB index in SSP2(1)
YY:
FB index in SSP1(2)
YY:
FB index in SSP1(1)
WW XX YY ZZ
WW:
FB index in 100MS (2)
XX:
FB index in 100MS(1)
YY:
FB index in 10MS
YY:
FB index in 5MS
WW XX YY ZZ
WW:
FB index in SUB4
XX:
FB index in SUB3
YY:
FB index in SUB2
YY:
FB index in SUB1
6F2T0207 (0.01)