Page 1
6F2S1916 (Rev. 0.5) INSTRUCTION MANUAL Interface unit GR 200 series (GIF200)
Page 2
6F2S1916 (0.5) Safety Precautions Before using this equipment, please read this chapter carefully. This chapter describes the safety precautions recommended when using the GR equipment. Before installing and using the equipment, this chapter must be thoroughly read and understood. Explanation of symbols used Signal words such as DANGER, WARNING, and CAUTION, will be followed by important safety information that must be carefully reviewed.
Page 3
6F2S1916 (0.5) CAUTION •Earth The earthing terminal of the equipment must be securely earthed. CAUTION •Operating environment The equipment must only be used within the range of ambient temperature, humidity and dust detailed in the specification and in an environment free of abnormal vibration. •Ratings Before applying AC voltage and current or the DC power supply to the equipment, check that they conform to the equipment ratings.
Page 4
For further information in terms of the disposal, the customer shall contact to a local dealer and sales staff at Toshiba Energy Systems & Solutions Corporation (Toshiba ESS, Japan).
6F2S1916 (0.5) Contents Introduction ............................1 Outline ............................. 1 Connection and signal-conversion ....................1 Settings and operations.......................... 2 Overview ............................2 Connection in C37.94 at ST connectors ..................2 Connection in G.703 at CN1 (D-sub) connector ................3 DC power at TB1 connector ......................3 LED indicators ..........................
6F2S1916 (0.5) Introduction Outline The optical interface unit (GIF200) is used to connect with the multiplexer (MUX), when the line protection relay (GRL200 IED having a protection-signaling module in ST port) is required to connect with the remote GLR200 IED in the switched communication network achieved with the MUX.
6F2S1916 (0.5) Settings and operations Figure 2.1-1 shows the outline of the GIF200 unit. Two optical modules (E/O and O/E with ST port) for the IEEE C37.94 and a CN1 (D-sub 25-pin or DB-25) socket for the ITU-T G.703 are provided;...
6F2S1916 (0.5) treatment or by exceeding the minimum bend radius of the fiber cable. Connection in G.703 at CN1 (D-sub) connector The CN1 (D-sub 25 pin / DB-25) connector is used for connection with the MUX over twist-pair cables, as shown in Figure 2.3-1 and Table 2.3-1. GIF200 CN1/G703 D-sub...
6F2S1916 (0.5) with each LED. GIF200 RX in C37.94 RX in G.703 TX in C37.94 TX in G.703 CF in C37.94 CLK in G.703 YAL in C37.94 Power Figure 2.5-1 Eight LED indicators on GIF200 Table 2.5-1 Meaning of LED indicators Type Color Function...
6F2S1916 (0.5) C37.94 frame from ‘0’ to ‘1’ for a return path from the GIF200 to the GRL2000. Incidentally, the GIF200 sets all ‘1’ bits for the frames (alarm indication signal (AIS)) from GIF200 to the MUX. Erroneous data with three yellow alarms (without LOS) (iii) When ‘Yellow alarm bit’...
6F2S1916 (0.5) IEEE C37.94 I/F ITU-T G.703 I/F Data with “Yellow Data based on alarm bit” G.703 Data based on Erroneous data G.703 GRL200 GIF200 unit Figure 2.7-2 O/E failure in GIF200 G.703 reception failure detected in GIF200 (iii) If the GIF200 does not receive any data from the MUX, the GIF200 unit sends TX data consisting of all ‘1’...
6F2S1916 (0.5) Telecommunication IEEE C37.94 I/F ITU-T G.703 I/F network Data based on C39.74 Data consisting of all Data based on ‘1’ bits C39.74 No transmission GRL200 GIF200 unit Figure 2.7-4 G.703 TX failure in GIF200 unit Bit synchronization for sending Synchronized multiplexing should be carried out with any data received from a number of GIF200 units.
6F2S1916 (0.5) Installation On receiving the GIF200 unit, carry out the acceptance inspection immediately. In particular, check for damage during transportation, and if any is found, contact the vendor. Always store the unit in a clean, dry environment. Mounting Refer to Appendix for details of mechanical fixings. Electrostatic Discharge CAUTION The printed circuit board (PCB) within the unit is not intended to be a removable module.
Page 15
6F2S1916 (0.5) potential as yourself. Do not place the PCB in a polystyrene tray. It is strongly recommended that detailed investigations on electronic circuitry should be carried out in a Special Handling Area such as described in the IEC 60747. GIF200 - 9 -...
6F2S1916 (0.5) Commissioning and maintenance The GIF200 unit should be commissioned in conjunction with the GRL200 IED with which it is specified. Test personnel must be familiar with general relay testing practices and safety precautions to avoid personal injuries or equipment damage. Precautions The unit is provided with a grounding terminal.
Page 21
Revision up Records Rev. and Section Approved Checked by Prepared Change place and contents Date (page) First issue T.Sugamoto T.Sugamoto T. Kaneko Oct. 23 2015 Oct. 23 Oct. 23 Oct. 22 Sec. 2.1 Modified descriptions about Clause 1.2.2 of Table2.1-1 T.Sugamoto T.Sugamoto T.Sugamoto...