Functional data (4/6)
Under/Over Frequency Protection (FRQ/DFRQ)
Under/Over frequency threshold:
DTL delay:
Undervoltage block:
Frequency
rate-of-change:
Reverse Active Power Protection (RP)
RP threshold:
DTL delay:
Drop-out/pick-up
ratio:
Undervoltage block:
Reverse Reactive Power Protection (RQ)
RQ threshold:
DTL delay:
Drop-out/pick-up
ratio:
Undervoltage block:
Automatic Transfer Operation (ATO)
Number of ATO commands
Checking time for ATO ready
ATO reset time
Output judgement time for ATO command
Pulse width of ATO command
Current change detection relay (OCDATO)
Prolonged time of OCDATO relay
Overcurrent relay (OCATO)
Undervoltage relay (UVATO1)
Undervoltage relay (UVATO2)
Motor Start Protection (Mot-StPro)
Motor start protection time:
Thermal overload Protection for Motor Protection (Mot-THM)
Thermal setting (THM =
Time constant ():
Time constant in radiation state ():
Thermal alarm:
Stalled Motor Protection (Mot-Stall)
Overcurrent threshold:
DTL delay:
Locked Rotor Protection (Mot-LKRT)
Motor start-up current:
Thermal level (rate of Mot-THM):
Allowable locked rotor time:
Restart Inhibit Function (Mot-THSR, Mot-STPH)
Limit number for starts per hour:
-10.00 – +10.00Hz in 0.01Hz steps
0.00 – 300.00s in 0.01s steps
40.0 – 100.0V in 0.1V steps
0.1 – 15.0Hz/s in 0.1Hz/s steps
-1500.0 – -5.0W in 0.1W steps
0.00 – 300.00s in 0.01s steps
50 – 98% in 1% steps
5.0 – 130.0V in 0.1V steps
-1500.0 – -5.0 var in 0.1var steps
0.00 – 300.00s in 0.01s steps
50 – 98% in 1% steps
5.0 – 130.0V in 0.1V steps
1 – 5
0.00 – 300.00s in 0.01s steps
0.00 – 310.00s in 0.01s steps
0.00 – 300.00s in 0.01s steps
0.00 – 10.00s in 0.01s steps
0.05 – 5.00A in 0.01A steps
0.00 – 100.00s in 0.01s steps
0.02 – 150.00A in 0.01A steps
5.0 – 130.0V in 0.1V steps
5.0 – 130.0V in 0.1V steps
0.10 - 300.00s in 0.1s steps
k.IFLC):
0.40 – 10.00A in 0.01A steps
0.5 – 500.0 min in 0.1min steps
0.5 – 500.0 min in 0.1min steps
50 – 100% in 1% steps
0.10 – 50.00A in 0.01A steps
0.00 – 300.00s in 0.01s steps
0.10 – 100.00A in 0.01A steps
50 – 1000% in 1% steps
1 – 300s in 1s steps
1 – 60 in 1 steps
- 1149 -
6F2T0207 (0.01)
GRE200 (5,6)