12.
PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
ID
Ed
Gs10
1,2 Max number of dataset members
Gs11
1 Is Fixed-length encoded GOOSE supported
Gs12
2 Is IEC 62351-6 security supported
Are subscribed GOOSE with ndsCom=T
Accepted.
1,2
13.
PIXIT for GOOSE performance
ID
Ed
Gf1
1,2 Performance class
Gf2
1,2 GOOSE ping-pong processing method
Gf3
1,2 Application logic scan cycle (ms)
Maximum number of data attributes in
GOOSE dataset (value and quality has to be
counted as separate attributes)
Gf4
1
Description
<additional items>
Description
- 1093 -
Value / Clarification
64
Y
N
GOOSE subscribe quality
information will become
QUESTIONABLE
INACCURATE (=1100 0000 0100 0).
GOOSE status change is ignored.
The behavior can be changed by
modifying PLC logic.
Value / Clarification
P1(Ed.2) for
System/LLN0$GO$goST
P3(Ed.2) for all other GOOSE
Scan cycle based
Max. .... 200ms
Min.
1.38ms in 60Hz
The dataset for
System/LLN0$GO$goST is fixed,
and it contains 32 data attributes.
All other dataset for GOOSE can be
configurable, and there is no
particular limitation about the
maximum number of data
attributes. However, the dataset
definition shares the same dynamic
memory area as other data model
definitions such as LN, RCB, etc., so
it is affected by them.
6F2T0207 (0.01)
(PIXIT Ed.1&Ed.2)
|
GRE200 (5,6)