Toshiba GR-200-5 Instruction Manual page 1039

Multi functional protection ied

Advertisement

The following shows how to operate in this screen.
TimeSyncSrc menu
Time SyncSrc (Time Synchronization Source) can be changed by the following procedure.
Time Sync
10:48
1/4
_TimeSyncSrc
SNTP
SNTP
On
BI SYNC
Off
MODBUS SYNC
Off
IRIG SYNC
Off
TimeSyncSrc
10:48
1/5
---
_SNTP
BI
MODBUS
IRIG-B
By using time synchronization via Ethernet with a SNTP server, the user can connect up to a
maximum of four SNTP servers. If more than one SNTP is used, the priority of the servers can
be decided in ascending order of synchronized stratum value (in order of higher-accuracy) and
select the server with the smallest value.
SNTP setting
IP address of SNTP server can be set by the following procedure.
Time Sync
10:48
1/4
TimeSyncSrc
SNTP
_SNTP
On
BI SYNC
Off
SNTP
10:48
1/4
_Server1
0. 0. 0. 0
Server2
0. 0. 0. 0
Server3
0. 0. 0. 0
1) Move cursor to the TimeSyncSrc menu and press ENTER.
+
+>
+>
+
+>
2) The TimeSyncSrc menu is composed of "---", SNTP, BI,
MODBUS and IRIG-B.
Note: When "---" is selected, it means that time synchronization is
not operated.
1) Confirm that the SNTP synchronization function is set for On.
Subsequently move cursor to the SNTP menu and press ►.
+
+>
+>
2) Move cursor to desired server number and press ENTER.
+
+
+
- 1019 -
6F2T0207 (0.01)
GRE200 (5,6)