Toshiba GR-200-5 Instruction Manual page 455

Multi functional protection ied

Advertisement

From SOFTSW*1
Command blocking
Double Command Blocking detected*2
Other devices traveling detected*3
Function "Automatic sequence control" is in progress
ASEQ_MULTI_SEL
From TRC*4
Tripping *4 ("General trip")
Additional condition (PLC#1 connection point)
511001 800201EE61
DPSY01IN_TMP_31
User configurable condition (PLC#2 connection point)
511001 810201EE62
DPSY01IN_TMP_32
Control hierarchy (e.g. 43RL) (PLC#3 connection point)*9
511001 820201ED50
DPSY01IN_TMP_28
From CMNCTRL
IED serious error detected
Figure 4.1-13 Select condition logic for 'Closing/Open' in DPSY01
Note: "Command Blocking" disables any operation except its own; the "Command
1
Blocking" is initiated by the status of "CBK" in a software switch controller
(SOTFSW). The IEC 61850 standard defines "Command Blocking" as "CmdBlk".
For more information on "CBK", see Chapter
Software switch controller. See the signal "
Note: "Double Command Blocking" (DCB) is an operation philosophy. It can be used to
2
protect the substation. The user can program it using GR-TIEMS. The DCB
operating signal is denoted as "DCB RCV OR) in Table 4.1-6.
Note: If the event "device-travelling" is detected, it indicates that another operator is
3
changing the status of a device. Thus, the IED should inhibit the operation of any
device for the duration that the event is detected. The detecting signal is denoted
as "Travelling OR" in Table 4.1-6.
Note: If the issue of a trip command is executed by the IED, any control operation is
4
blocked until the trip operation is completed. If an IED includes a relay
application, the trip command is issued at the output-point "GEN.TRIP" in Table
4.1-6.
Note: Criteria "unmatched conditions" are decided when "Test-bit status" in a command
5
is not identical to the "IED test status".
Note: The "Event suppression" function can detect chattering on BI circuits. (See section
6
DPSY01 function (Function ID: 511001)
CBK_STATE
DCB RCV OR
Traveling OR
Unmatched condition detected *5
Event suppression detected *6
= DPSY01_F_QLT_SPP
GEN. TRIP
BI board connection error detected*7
= DPSY01_F_BI_ERR
Command "Open control" received
Command "Closing control" received
DPSY01_3PH_STATE
(511001 3102011001)
[SCDEN]*8
OFF
[DPOS01-LGSLFFCT]
Fixedlogic
Users must setup this condition correctly
SERI_ERR
[DPSY01-CTREN]
On
1≥
(511001 8102011F5F)
(511001 8202011F60)
&
&
received
Same Directional
Controlling Event
Control and monitoring application:
"S4301_STATE" of Table 4.1-6.
- 435 -
6F2T0207 (0.01)
1≥
&
&
To selection logic
Select condition
&
&
*10
GRE200 (5,6)
BI board connecti
Event supp
Unmatched con