Multi functional protection ied

Advertisement

Transferred information during fault
The IED can transfer the information for the fault duration in the IEC61850 communication†.
†Note: The transferring is only available in "Edition1 with option" or "Editon2" of the
IEC61850. For the information about the option, see Chapter
protocol: IEC 61850 communication: About protocol
Transferred metering values
8.4.1
Table 8.4-1 shows transferring information during the fault†. When the IED is running on the
IEC61850 Edition1 option, these signals should be mapped for Private Object AnInDatUpd.
When the IED is running on the IEC61850 Editon2, they should be mapped for Normal Object
AnIn.
Table 8.4-1 Transferred values taken during the fault
Items
Ia (Primary)
Ib (Primary)
Ic (Primary)
Ie (Primary)
Ise (Primary)
I1 (Primary)
I2 (Primary)
I0 (Primary)
Vab (Primary)
Vbc (Primary)
Vca (Primary)
Va (Primary)
Vb (Primary)
Vc (Primary)
Ve (Primary)
Vs (Primary)
I2/I1
THM-Capacity
Note: See section 8.1.1(vi) about the information about fault recording quantities. To
find Data ID, see section 8.4.4.
§Note: Model is chosen by the number of at ordering codes at positions T. See Software
selection in
Signals
Unit
names
A
FLTMS0001
A
FLTMS0004
A
FLTMS0007
A
FLTMS0010
A
FLTMS0013
A
FLTMS0016
A
FLTMS0019
A
FLTMS0022
V
FLTMS0025
V
FLTMS0028
V
FLTMS0031
V
FLTMS0034
V
FLTMS0037
V
FLTMS0040
V
FLTMS0043
V
FLTMS0046
FLTMS0049
FLTMS0052
%
Appendix: Ordering
- 761 -
, separately (→p. 877).
Model GRE200-
5
NA
(→p. 1133).
6F2T0207 (0.01)
Communication
§
6
NA
GRE200 (5,6)