Download Print this page

Toshiba GR-200-5 Instruction Manual page 1160

Multi functional protection ied

Advertisement

Appendix 8 Technical data
Technical data (1/3)
Analog Inputs
Rated current
Phase Current (In)
Zero sequence Current (Ien)
Zero sequence Current for SEF (Isen)
Rated voltage (Vn, Ven, Vsn)
Rated Frequency
Overload Rating
Phase Current
Zero sequence Current
Zero sequence Current for SEF
Voltage
Burden
Phase current
Zero sequence Current
Zero sequence Current for SEF
Voltage
Power Supply
Rated auxiliary voltage
Superimposed AC ripple on DC supply
Supply interruption
Power consumption
1A or 5A (selectable)
1A or 5A (selectable)
0.2A
100V to 120V
50Hz or 60Hz (selectable)
4 times rated current continuous
5 times rated current for 3 minutes
6 times rated current for 2 minutes
30 times rated current for 10 seconds
100 times rated current for 1 second
250 times rated current for one power cycle (20 or 16.6ms)
Rated current continuous at In = 5A
20 times rated current for 1 second at In = 5A
10 times rated current continuous at In = 0.2A
2 times rated voltage continuous
2.5 times rated voltage for 1 second
 0.2VA at In = 5A
 0.4VA at In = 5A
 0.1 VA at In = 0.2A
 0.1VA at Vn
24/48/60Vdc (Operative range: 19.2 – 72Vdc)
110-250Vdc (Operative range: 87.5 ~ 300Vdc)
100-240Vac (Operative range: 80 ~ 288Vac)
 15%
 20ms at 110Vdc
 21W (quiescent)
 29W (maximum)
- 1140 -
6F2T0207 (0.01)
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6