Download Print this page

Toshiba GR-200-5 Instruction Manual page 1066

Multi functional protection ied

Advertisement

GOOSE receiving block (GOSUBBLK)
(ii)
This is used for receiving or rejecting GOOSE subscription information from another IED for
the test of bad receptions. See Chapter
(→p. 902).
Test flag cancel (S-TestFlagCancel)
(iii)
Test flag in the communication packet will be removed unconditionally, when On is set for
setting [Test flag].
Test for all communication (TestFlag-EN)
(iv)
Setting [TestFlag-EN]=On allows to set test flags at all communication protocol.
Test for relay application
14.4.2
Auto monitoring function (A.M.F)
(i)
Issuing alarms will be blocked when Off is set for [A.M.F]. For the content about the monitoring
function, see Chapter
Test of cold load protection (CLP-Test)
(ii)
STATE0 or STATE3 will be selected temporally, if STATE0 or STATE3 is set for setting [CLP-
TEST]. See Chapter
Thermal overload function test (THM-Test, THM-IP)
(iii)
Setting [THM-Test]=On allows to have a test value for the pre-load current (Ip). The Ip value
is discussed in Chapter
SOTF test (SOTF-Test)
(iv)
Setting [SOTF-Test]=On allows to generate the cold load condition mandatorily for testing,
which is discussed in Chapter
Under voltage test (UV,UVS-Test)
(v)
Settings [UV-Test] and [UVS-Test]=On is not to operate UV and UVS blocking elements for
testing. See Chapter
142 or 154).
ARC shot number test (SHOTNUM-Test)
(vi)
Setting [SHOTNUM-Test] is provided so that the user can have the preferred shot number for
the ARC test, which is discussed in Chapter
Communication protocol: IEC 61850 communication
Automatic supervision function
Relay application: Cold load protection
Relay application: Thermal overload function
Relay application: Switch on to fault
Relay application: Phase
- 1046 -
(→p.
).
799
for more detail (→p. 130).
Phase-to-phase under-voltage protection
or
Relay application: Autoreclose
6F2T0207 (0.01)
(→p. 122).
(→p. 113).
(→p. 232).
GRE200 (5,6)
(→p.

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6