Download Print this page

Toshiba GR-200-5 Instruction Manual page 1107

Multi functional protection ied

Advertisement

9.
PIXIT for Reporting model
ID
Ed
The supported trigger conditions are
(compare PICS)
Rp1
1
The supported optional fields are
Rp2
1
Can the server send segmented reports
(when not supported it is allowed to refuse an
Rp3
1,2
association with a smaller than minimum PDU
size)
Mechanism on second internal data change
notification of the same analogue data value
Rp4
1,2
within buffer period (Compare IEC 61850-7-2
$14.2.2.9)
Multi client URCB approach
Rp5
1
(compare IEC 61850-7-2:2003 $14.2.1)
Rp6
-
What is the format of EntryID
What is the buffer size for each BRCB or how
Rp7
1,2
many reports can be buffered
Pre-configured
Rp8
-
dynamic, compare SCL report settings
May the reported data set contain:
Rp9
1
- structured data objects
- data attributes
What is the scan cycle for binary events
Rp10
1,2
Is this fixed, configurable
Description
RCB
attributes
that
- 1087 -
Value / Clarification
integrity
data change
quality change
data update
general interrogation
sequence-number
report-time-stamp
reason-for-inclusion
data-set-name
data-reference
buffer-overflow
entryID
conf-rev
segmentation
Y
Send report immediately
Each URCB is visible to all clients
Deprecated
For example, LLN0$ST$Health
can be stored 408 events.
are
Deprecated
Y
Y
More than 1.6 milliseconds
Configurable
6F2T0207 (0.01)
(PIXIT Ed.1&Ed.2)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
GRE200 (5,6)