Binary Input
10:48
Slot#1
Slot#3
Figure 12.8-5 Binary input menu
Figure 12.8-6 is a case when IO#3 (Slot#03) is selected.
Slot#3
10:48
BIF OP
Slot3-BIO1-SET
Slot3-BIO2-SET
Slot3-BI03-SET
Figure 12.8-6 Setting menu for Slot #3 module
For example, if the user wishes to simulate binary input circuit #1 (BI1) on the
BIO1A module at IO#3 slot, the user can select SLOT3-BI01-SET screen, as shown
in Figure 12.8-6).
Slot3-BIO1-SET
10:48
Figure 12.8-7 Setting menu after selecting "Slot #3-BIO1-SET"
The user can then make the following selections on the screen and configure the
items required for simulation.
• ON:
BI1 output is set forcibly to ON(Logic level=high(1)) regardless of
the actual input signal.
• OFF:
BI1 output is set forcibly to OFF(Logic level=low(0)) regardless of
the actual input signal.
• Normal:
Actual inputs are applied.
Use the screen shown in Figure 12.8-7 only to configure the BI signals for the
simulation test. This does not start the simulation.
The setting menu is shown in the manner of the screen illustrated in Figure 12.8-7,
if the user needs to configure an Input Circuit other than BI01 (BI02 to BI18 in the
1/2
>
>
1/19
+
+
Normal
+
Normal
+
1/3
Normal
Off
On
- 1026 -