Detail settings for the heat maps
L A maximum of 24 heat maps are stored. After that, the
recording is automatically interrupted.
8.4 Parameters
Temperature
– Display of the currently measured temperature.
– The measured value can be corrected by entering a
new actual temperature.
L Before the temperature calibration can be carried out, the
presence detector must be in operation for at least 30
minutes (with a well insulated ceiling at least 2 hours).
Brightness zone x
– Display of the currently measured brightness.
– The measured value can be corrected by entering
a new light value.
L Perform the calibration at an ambient brightness of
≥ 250 lux.
You must proceed as follows ...
Select parameter <brightness zone X>.
▻ Pop-up window opens.
Start/cancel recording
Export of the heat maps
selected below
Deletion of the heat
maps selected below
Place the smartphone or tablet in the corresponding zone.
Select the Apply button.
▻ Measured lux value (from smartphone/tablet) is
entered in the field <set light level value>.
Go out of the zone.
Finally, press the OK button.
L The brightness calibration must be carried out for each
zone.
L Instead of the brightness value of smartphones/tablets, a
lux value (measured by a luxmeter)´can also be entered
manually.
L If the local conditions change considerably, the brightness
has to be recalibrated.
L If the smartphone/tablet does not have an integrated
brightness sensor, it will be indicated by an error message.
Manual calibration with an external lux meter can still be
carried out.
Installation height
– Selection of installation height of detector
– Selection of 2.5 – 4.5 m
Sensitivity of the detector
The detector has 5 sensitivity levels:
— 1 very insensitive
— 2 insensitive
— 3 standard
— 4 sensitive
— 5 very sensitive
L The sensitivity refers to all zones.
Room definition
Specification of the room in which the presence detector is
used:
Standard:
Standard rooms such as office, corridor,
etc.
Meeting room:
Der The detector is installed in a meeting
room and thus adapted to the conditions
of this room, with a
focus on counting people.
L The room definition refers to all zones.