Lenovo 7Y45 Instructions Manual page 37

Messages and codes reference
Hide thumbs Also See for 7Y45:
Table of Contents

Advertisement

User Action:
Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place.
3. Make sure that the room temperature is in the range in the operating specifications.
• FQXSPCA0017M: Sensor [SensorElementName] has transitioned to critical from a less severe
state.
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0522
User Action:
Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place.
3. Make sure that the room temperature is in the range in the operating specifications.
• FQXSPCA0019N: Sensor [SensorElementName] has transitioned to non-recoverable from a less
severe state.
This message is for the use case when an implementation has detected a Sensor transitioned to non-
recoverable from less severe.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0524
User Action:
Complete the following steps until the problem is solved:
1. Check the XCC event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
correctly installed in place.
3. Make sure that the room temperature is in the range in the operating specifications.
• FQXSPCA2002I: Numeric sensor [NumericSensorElementName] going low (lower critical) has
deasserted.
This message is for the use case when an implementation has detected a Lower Critical sensor going low
has deasserted.
Severity: Info
.
Chapter 2
XClarity Controller events
33