Download Print this page

Frymaster FilterQuick easyTouch FQG100T Installation, Operation And Maintenance Manual page 21

Hide thumbs Also See for FilterQuick easyTouch FQG100T:

Advertisement

IRELAND (IE)
UNITED KINGDOM (UK)
Required airflow for the combustion air supply is 2m
1. Connect the quick-disconnect hose to the fryer quick-disconnect fitting under the front of the
fryer and to the building gas line. NOTE: Quick disconnect hoses are not supplied to CE or
UKCA marked fryers.
NOTE: Some fryers are configured for a rigid connection to the gas supply line. These units are
connected to the gas supply line at the rear of the unit.
When using thread compound, use very small amounts on male threads only. Use a pipe
thread compound that is not affected by the chemical action of LP gases (Loctite™ PST56765
Sealant is one such compound). DO NOT apply compound to the first two threads. Doing so
may allow some of the compound to enter the gas stream, resulting in clogging of burner
orifices and/or the control valve.
2. Open the gas supply to the fryer and check all piping, fittings, and gas connections for leaks. A
soap solution should be used for this purpose.
3. If the unit is not already plugged in, plug in the fryer to ensure the fryer drain valve is closed
and fill the frypot with water or oil to the bottom OIL LEVEL line at the rear of the frypot
4. Clean, and fill frypot(s) with cooking oil (see Equipment Setup and Shutdown Procedures in
Chapter 3).
"Dry-firing" your unit will cause damage to the frypot and can cause a fire. Always
ensure that cooking oil or water is in the frypot before firing your unit.
5. Light the fryer following the procedures that are described in the "Lighting Instructions" found
in Chapter 3 of this manual.
6. Confirm that the arrow forged into the bottom of the regulator body, which indicates gas flow direc-
tion, is pointed downstream towards the fryers. The air vent cap is also part of the regulator and
should not be removed. If a vent line from the gas pressure regulator is used, it should be installed in
accordance with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1-(latest edition) in the U.S. and appropriate national or European harmonized standards (EN) in
the European Union.
a) Regulators can be adjusted in the field, but it is recommended that qualified service personnel
adjust a regulator only if it is known to be out of adjustment or serious pressure fluctuations
have been found and cannot be solved another way.
b) Only qualified service personnel should make adjustments to the regulators.
UKCA Approved Gas Categories by Country
COUNTRIES
CATEGORIES
II2H3+
II2H3+
UKCA Standard
GAS
PRESSURE (MBAR)
G20
G30, G31
G20
G30, G31
DANGER
2-10
20
28-30, 37
20
28-30, 37
3
/h per kW.
.

Advertisement

loading