Lincoln Electric FineLine 170HD Operator's Manual page 102

Table of Contents

Advertisement

FineLine 170HD Plasma System
7.2.1 Event Log File
Each time the FineLine UI starts, it creates a log file in the following location:
C:\Users\Public\Documents\CutLinc\temp
Filename format is:
GHMI-Month-Day-Year-Hour-Min-Second.txt
Example: GHMI-09-09-2020-10-45-44.txt
Events are written chronologically into this file as they are generated.
7.2.2 Event Codes
Source HMI
Event Code
1
SYSTEM NOT READY
11
CUTLINC CONNECT FAILED
12
CUTLINC CONNECTION LOST
Source CLMI
Event Code
11
CUTLINC CONNECT FAILED
12
CUTLINC CONNECTION LOST
Source CLModel
Event Code
512
N2 PRES LOW
513
O2 PRES LOW
514
AIR PRES LOW
515
AR PRES LOW
516
H17 PRES LOW
This information is subject to the controls of the Export Administration Regulations [EAR]. This information shall not be provided to
non-U.S. persons or transferred by any means to any location outside the United States contrary to the requirements of the EAR.
Description
Description
Description
Page 102 of 132
BK8053-000111 Rev D
Possible Resolution
Check Ethernet connection. Check router.
Check Ethernet connection. Check router.
Possible Resolution
Check Ethernet connection. Check router.
Check Ethernet connection. Check router.
Possible Resolution
Check input gas pressure – pressure should
be within 105 – 140 psi
Check input gas pressure – pressure should
be within 105 – 140 psi
Check input gas pressure – pressure should
be within 105 – 140 psi
Check input gas pressure – pressure should
be within 105 – 140 psi
Check input gas pressure – pressure should
be within 105 – 140 psi