Pentair Fleck 3150 NXT Installer Manual page 98

Hide thumbs Also See for Fleck 3150 NXT:
Table of Contents

Advertisement

Installer manual Fleck 3150 NXT/NXT2 - Programming
Parameter
ASSISTANCE
NAME 1
ASSISTANCE
NAME 2
ASSISTANCE
PHONE
SYSTEM
NUMBER OF
TANKS
TRIP POINT #X -
LPM
TRIP POINT #X -
SERVICE
DURATION
TRIP POINT #X -
STANDBY
DURATION
VALVE
98 / 190
Options
-
-
-
4
Single unit (default)
5
Parallel interlock
6
Parallel series
regeneration
7
Alternating immediate 2 units.
8
Alternating delayed
9
Parallel with standby
14
On-demand
2 to 8
Valves in the system
1 to 7569
1 to 90
60 to 300
2510
2750
2850
2900/2910
3150
3900
2815
Definition
-
12 characters maximum.
-
-
14 characters maximum.
1 unit.
2 to 8 units.
2 to 8 units.
unit
This screen will not be displayed
for system type 4, 7 and 8.
l/min
System 14 only.
Even if maximum theoretical
programmable value is 9999 l/min
the controller will consider only up
to 7569 l/min.
Second
System 14 only;
Duration for which the service flow
rate must be greater than the
above trip point flow rate to cause
the next tank to move into service
position.
Second
System 14 only;
Duration for which the service flow
rate must be lower than the above
trip point flow rate to cause one of
the tank of the system to move
back into stand-by position.
-
Valve type.
(default)
-
-
-
-
-
Note
Ref. MKT-IM-010 / F - 16.01.2023