4

System sizing

4.1

Recommended Injector/DLFC/BLFC-Valve configuration

Brine
Tank
syst.
Diameter
[in]
3150/
24
1800
30
36
42
48
54
60
4.2

Sizing a softener (single unit)

4.2.1

Parameters to be considered

Whenever installing a softener, it is preferable to have full water analysis to ensure the inlet water
content will not affect the resin bed.
Tip
Please consult your resin manufacturer specification !
To ensure that no additional pretreatment prior to softening is required.
The below sizing method can be applied for both residential and industrial softeners.
The sizing of a softener must be based upon certain parameters:
• inlet water hardness;
• peak flow rate and nominal flow rate;
• service velocity;
• salt dosage.
The softening and regeneration reactions are driven under certain conditions. To allow these
reactions to take place, make sure that the velocity is convenient during the different phases for
proper ion exchange. This velocity is given in the resin manufacturer specifications sheet.
Depending on the inlet water hardness, the service velocity for standard softening must be
between:
Service velocity
[bed volume per hour]
8 - 40
8 - 30
Ref. MKT-IM-010 / F - 16.01.2023
Resin
volume
L
DF
Color
283 - 424
4
Green
284 - 425
5
Red
426 - 605
6
White
566 - 850
7
Blue
851 - 1200
8
Yellow
1201 -
9
Purple
1550
1551 -
10
Black
2000
Inlet water hardness
Installer manual Fleck 3150 NXT/NXT2 - System sizing
Injector
UF
Color
4
Green
5
Red
6
White
7
Blue
8
Yellow
[mg/l as CaCO
]
3
<350
350 to 450
DLFC
BLFC
[gpm]
DF [gpm] UF [gpm]
20.0
5.0
25.0
35.0
50.0
10.0
70.0
80.0
100.0
°f
°TH
<35
35 - 45
19.6 - 25.2
5.0
10.0
°dH
<19.6