Parameter data record
A.2 Parameter validation error
Error codes
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Table A- 3
Error codes for parameter validation
Error code in STATUS
parameter (hexadecimal)
Byte
Byte
Byte
Byte
0
1
2
3
DF
80
B0
00
DF
80
B1
00
DF
80
B2
00
DF
80
E0
01
DF
80
E0
02
DF
80
E1
00
DF
80
E1
12
DF
80
E1
13
DF
80
E1
1A
DF
80
E1
26
DF
80
E1
29
DF
80
E1
2C
DF
80
E1
2D
DF
80
E1
40
DF
80
E1
41
DF
80
E1
44
DF
80
E1
45
DF
80
E1
50
DF
80
E1
51
DF
80
E1
52
DF
80
E1
FF
56
Meaning
Data record number unknown
Length of data record incorrect
Slot invalid or not accessible
Wrong version
Error in the header information
Parameter invalid: No detailed information
available
Value in byte 4/32 invalid
"Signal type" parameter invalid
"Input delay" parameter invalid
"Reference speed" parameter invalid
"Increments per revolution" parameter invalid
"Signal evaluation" parameter invalid
Value in byte 5/33 invalid
Value in byte 27/55 invalid
Value in byte 28/56 invalid
Value in byte 26/54 invalid
Value in byte 29/57 invalid
"Maximum speed" parameter invalid
"Quick stop time (OFF3)" parameter invalid
"Ramp stop time (OFF1)" parameter invalid
Conflict with the isochronous times configured
in the hardware configuration.
To correct and avoid errors
Enter valid number for data record
Enter valid value for data record length.
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC instruction.
Check byte 0.
Enter valid values.
Check byte 1.
Correct length of parameter blocks.
Check all parameter values.
Enter value 000
.
B
Enter valid parameter value.
Enter valid parameter value.
Enter parameter value from range 1.0 to 20000.0
taking into account the dependencies (Page 52).
Enter parameter value from range 1 to 1000000
taking into account the dependencies (Page 52).
Enter valid parameter value.
Enter value 0
.
B
Enter value 00000
.
B
Enter value 00001
.
B
Enter value 00000
.
B
Enter value 00010
.
B
Enter parameter value from the valid range (Page 52)
in each case.
Enter parameter value from range 1 to 65535
Enter parameter value from range 1 to 65535
Enter suitable isochronous times in the hardware
configuration.