Error codes
G1_XIST2 can contain the following error codes:
Error
code
1
H
3
H
4
H
5
H
6
H
7
H
8
H
F01
F02
Technology module TM PTO 2x24V (6ES7138‑6EB00‑0BA0)
Equipment Manual, 09/2021, A5E50983437-AA
Name
Sensor group error
Sensor pause failed
Reference mark detec-
tion aborted
Read reference mark
aborted
Measuring input value
acquisition aborted
Read measuring input
value aborted
Absolute value acquisi-
tion aborted
Command not sup-
H
ported
Sign-of-life error (Mas-
H
ter Sign-Of-Life)
Meaning
G1_XIST1 is invalid. A short-circuit or overload has occurred at the
digital output.
A sensor pause (Sensor parking) is not supported.
The Function_2_Request, Function_3_Request or Func-
tion_4_Request bit was set to 1 while "Reference mark search"
was active.
The Mode bit was set to 1 while the "Reference mark search"
was active.
CPU STOP while "Reference mark search" was active.
The Mode bit was set to 1 while the reference mark was
shown in G1_XIST2.
CPU STOP while the reference mark is displayed in G1_XIST2.
The Function_3_Request or Function_4_Request bit was set to
1 while "Measurement on the fly" was active.
The Mode bit was set to 0 while the "Measurement on the fly"
was active.
CPU STOP while "Measurement on the fly" was active.
The Mode bit was set to 0 while the measuring input value was
shown in G1_XIST2.
CPU STOP while the measuring input value was displayed in
G1_XIST2.
The Request_Absolute_value_Cyclically bit is not supported by the
module. The module returns only incremental encoder values.
The command is not supported by the module.
The number of tolerated errors of the Master sign-of-life (control
value Master_Sign-Of-Life) was exceeded.
Configuring/address space
4.4 Control and feedback interface
37