Input delay
Tolerated number of
sign-of-life errors
Due to the limited number of parameters at a maximum of 244 bytes per station with a PROFIBUS
1
GSD configuration, the configuration options are restricted. This parameter is visible. The other pa-
rameters are preassigned in the module with the default setting. If your PROFIBUS master supports
the "Read/write data record" function, you can set the other parameters using data record 128.
The following table shows the calculation of the value range of the maximum speed:
Signal evaluation
"Single"
0.1 Hz * 60 / (increments
per revolution)
Technology module TM PTO 2x24V (6ES7138‑6EB00‑0BA0)
Equipment Manual, 09/2021, A5E50983437-AA
Parameter
Value range of the maximum speed
Low limit
Signal evaluation
"Quadruple"
0.1 Hz * 60 *4 / (increments
per revolution)
Value range
•
None
•
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
0...1...65535
(the smaller of the two values applies)
Signal evaluation
"Single"
•
2 * reference speed
•
200000 Hz * 60 / (incre-
ments per revolution)
Configuring/address space
4.2 Parameter setting
Scope
Channel
Channel
High limit
Signal evaluation
"Quadruple"
•
2 * reference speed
•
200000 Hz * 60 *4 /
(increments per revolu-
tion)
27