Compressor Thermal Protector; Checking Procedures - Daikin RXTA30B2V1B Service Manual

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

4
|
Components

4.3 Compressor thermal protector

4.3.1 Checking procedures

To perform a mechanical check of the compressor thermal protector
Service manual
68
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
Prerequisite: Remove the compressor insulation.
1 Remove the cover of the compressor wire terminals.
a Compressor wire terminals cover
2 Remove the compressor thermal protection with bracket from the
compressor.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"4.17 Plate
a
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
4
work" [
 144].
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02