To perform an electrical check of the compressor
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 57].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
Action
Perform an electrical check of the
compressor, see
4
procedures" [
Replace the compressor and/or
damaged dampers, see
4
procedures" [
a
4
Components
|
"4.2.1 Checking
 57].
"4.2.2 Repair
 62].
"4.2.1  Checking
Service manual
59