6.3.3 Messages list

Code
4002
WATCHDOG RESET
4003
SENSOR AUTO-CALIBRATION ERROR
4111
RECTIFIER UTILITY OK
4119
BATTERY TEST STARTED
4120
BATTERY TEST STOPPED
4122
MANUAL BOOST CHARGE START
4123
AUTOMATIC BOOST CHARGE START
MANUAL/AUTOMATIC BOOST CHARGE
4124
4144
4145
4148
BATTERY CHARGER ON
4149
BATTERY CHARGER OFF
4161
4162
4163
GENERATOR ON
4164
GENERATOR OFF
4302
INVERTER CANNOT BE TURNED ON
Modifications reserved
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
Message
STOP
BOOSTER ON
BOOSTER OFF
RECTIFIER ON
RECTIFIER OFF
Description
The microprocessor has detected an incorrect
operation:
Transfers the load on utility and performs a
program reset.
The Inverter will restart automatically and will
supply the load.
The voltage/current reading were not correctly
calibrated when the UPS was switched on.
Rectifier Input Utility is again within the admitted
tolerance (voltage, frequency and phase).
Start of Manual or Automatic Battery Test.
End of Manual or Automatic Battery Test.
Recharging has been manually activated from
the control panel, bringing the final load up to the
value of the respective parameter.
After the battery has discharged, an automatic
boost charge has started to recharge the battery
based on pre-defined settings.
The automatic boost charge has finished. The
battery's voltage will return to the maintenance
value.
A manually activated boost charge will finish if: it
is manually interrupted, the initial timer setting
has expired, or the rectifier is not functioning
correctly (Alarm 4140).
The
battery
voltage
maintenance value.
The booster is switched ON.
It transfers energy from the battery to the DC-
link.
The booster is switched Off.
The battery charger is switched on and is
charging the battery.
The battery charger is switched off.
Rectifier started.
Rectifier shut-down.
Customer Interface (X1 - 11, 22) received a Gen-
set ON signal.
Operating
mode
depend
Parameters.
Customer Interface (X1 - 11, 22) received a Gen-
set OFF signal.
Function Bypass enabled depends on setting of
Parameter.
Inverter cannot be switched on because one of
the following conditions is still present:
- Overtemperature
- K7 opening Failure
- Low Battery Voltage - High Battery Voltage
- Inverter Fuses
- DC Low
- Overload
- EPO - Emergency Power Off
User Manual TLE Scalable Series 40 - 150 UL S1
will
return
to
the
on
setting
of
Page 39/90