GE FGC TLE Series Manual page 345

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

Technical Specifications - 480/277 VAC Applications
Power
Output Power Rating (kVA)
Rating**
Output Power Rating (kW)
Energy
eBoost Mode Efficiency at 50% Load
Usage
eBoost Mode Efficiency at 100% Load
eBoost Mode BTU/hr at 100% Load
Dbl Conv Mode Efficiency at 50% Load
Dbl Conv Mode Efficiency at 100% Load
Dbl Conv Mode BTU/hr at 100% Load
Physicals
Dimensions, w x dp x h (in.)
Weight, module only (lbs)
Input
Voltage
Topology
Dual Input Capable
Voltage Range (w/o battery discharge)
Power Factor (lagging)
Current THD
Frequency
Output
Voltage
Topology
Frequency
Crest Factor
Static Voltage Regulation
100% Step Load Voltage Regulation
100% Linear Load Voltage Distortion
100% Non-Linear Load Voltage Distortion
eBoost Transfer Time
Overload Capability / Inverter
Overload Capability / Static Bypass
Battery
Compatible Technologies
Plant
Float Voltage
Recharge Time
General
Audible Noise
Audible Noise (eBoost Mode)
Ambient Operating Temp
Humidity
Listings / Registrations
Enclosure
RFI / Surge Protection
Communication / Connectivity
Color
Warranty
For more technical information, please refer to applicable product Technical Datasheet
* = estimated data. Consult factory for updated information.
** product availability: 1250-1500 kW UPS (Q2 2015)
13
13
225
250
400
225
250
400
98.6%
98.7%
98.2%
98.8%
98.9%
98.6%
9,325
9,488
17,977
96.6%
96.7%
96.6%
96.5%
96.4%
96.5%
27,845
31,856
48,038
44.1 x 34 x 75
63.8 x 34 x 75
1,323
1,323
2,756
480VAC, 3ph, 4 wire + ground OR 3 wire + ground
Remove internal jumper cables for separate inputs to Rectifier & Static Bypass
480VAC, 3ph, 4 wire + ground OR 3 wire + ground
< 2msec transfer to Inverter, within ITI/CBEMA voltage compliance curve
110% continuous ; 150% for 1 minute
10X discharge time (at 30min battery runtime)
75 db(A) at 5 ft
75 db(A) at 5 ft
65 db(A) at 5 ft
66 db(A) at 5 ft
UPS Module: 32 to 104 degrees F (0-40 degrees C)
ETL as tested to UL1778 / IEC62040 / ISO 9001
RS232, programmable contacts, programmable relays, iUPSguard, optional SNMP & Modbus
12mo after startup or 18mo after shipment (whichever first). Extended warranties available.
500
750
1000
500
750
1000
98.3%
98.2%
98.4%
98.8%
98.8%
98.9%
20,722
31,082
37,951
96.5%
96.5%
96.4%
96.3%
96.3%
96.2%
63,712
98,325
134,783
118x34x75
143.5x34x75
2,756
4,520
5,200
IGBT Rectifier
-15% to +15%
0.99
< 5.0%
60 Hz +/- 10%
PWM 3-Level IGBT Inverter
50/60Hz
3 : 1
+/- 1%
+/- 3%
<3.0% THD maximum
<5.0% THD maximum
125% / 1 min ; 150% / 30 sec
VRLA, Wet Cell, NiCad
540 VDC , 240 cell system
78 db(A) at 5 ft
68 db(A) at 5 ft
0-95% non-condensing
IP20 and NEMA PE-1
EN50091-2 / IEC 62040-2
RAL 9005 Black
Name of Document
1250
1500
1250
1500
98%+
98%+
98%+
98%+
87,041*
104,448*
96%+
96%+
96%+
96%+
177,708*
213,250*
200 x 34 x 75 *
5,977*
6,577*
78 db(A) at 5 ft
68 db(A) at 5 ft
|
www.gecriticalpower.com