GE FGC TLE Series Manual page 72

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

GENERAL DATA
Topology
Nominal output apparent power
from PF=0.6 lag. to PF=0.9 lead.
Nominal output active power at PF=1
Efficiency at 100% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
Efficiency at 75% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
Efficiency at 50% load PF=0.9 lag. / 1 in VFI
& PF=1 in Eco-Mode
Audible noise level
Battery type
Operating temperature range
Storage temperature range
Max. altitude without power derating
Power derating (according to EN/IEC 62040-
3)
Protection degree
Standards
EMC (Electromagnetic Compatibility)
Electrostatic discharge immunity
Internal protection
Transport
Color
Installation
Service access
External cable connections
Cooling
Paralleling (RPA version)
Eco-Mode Operation
RECTIFIER
Rectifier bridge
Standard input voltage
Other input voltages
Input frequency
Power factor
Input current THD
Inrush current
Power walk-in
Output voltage tolerance
Battery voltage ripple
Battery current ripple
Battery charging characteristic
Battery charging current limit
Input power data
Input power at inverter nominal load and charged battery
Max. input power at inverter nominal load and max. battery recharge current
Standard battery charging current at the beginning of battery recharge at
nominal load (programmable)
UPS OUTPUT POWER CAPABILITY
Output UPS power versus power factor for:
Inductive loads
Resistive loads
Capacitive loads
Modifications reserved
GE_UPS_TDS_TLE_SUL_40K_M15_US_1US_V010.docx
Critical Power
VFI, double conversion
KVA
kW
VFI
95.6 / 95.5 95.6 / 95.5 95.7 / 95.6 95.6 / 95.5 95.6 / 95.5 95.6 / 95.4
%
Eco-Mode
98.6
VFI
95.7 / 95.6 95.7 / 95.6 95.8 / 95.7 95.8 / 95.7 95.8 / 95.7 95.9 / 95.7
%
Eco-Mode
98.3
VFI
95.2 / 95.1 95.6 / 95.5 95.6 / 95.5 95.7 / 95.6 95.7 / 95.5 95.9 / 95.7
%
Eco-Mode
97.7
dB(A)
Valve regulated lead-acid (VRLA), vented lead-acid, NiCd
UPS: 32°F ÷ 104°F / 0°C ÷ 40°C (up to 122F / 50°C subjected to conditions)
UPS: -13°F ÷ +131°F
-25°C ÷ +55°C
1000m
1500m: -2.5%
/
IP 30 (IEC 60529 - ANSI/NEMA 60529)
UL 1778 UL marking
EN/IEC 62040-2 Category C3 (Category C2 as option)
4kV contact / 8kV air discharge
All internal live parts shrouded
On pallet- Cabinet suitable for handling by forklift
RAL 9005 (black)
Minimum distance from the wall 2" / 5 cm and floor fixed
Front and top access only
Bottom at the front of the cabinet or top with lateral sidecar
Enforced ventilation with fan failure detection
Up to 6 units for redundancy or capacity in RPA configuration (option)
Standard
Three phase, IGBT rectifier, overtemperature protection
Nominal: 3 x 480V + N
Rectifier accepted ph-ph voltage range: 410V ÷ 550V (wider voltages subject to de-rated loads)
On request
60 Hz +/-10% (54 ÷ 66 Hz)
0.99
<3%
Limited by soft-start circuit
15 seconds (programmable)
+/- 1%
<1%
Max. 5% the battery capacity [Ah], expressed in A
IU (DIN 41773), T° compensated floating voltage
Programmable
at PF=0.9 lag.
at PF=1.0 lag.
40
50
80
40
50
80
98.8
98.8
98.4
98.5
98.0
98.2
Battery: -4°F ÷ +104°F
-20°C ÷ +40°C
2000m: -5%
/
2500m: -7.5%
kW
40
38.1
kW
42.4
kW
48.5
A
12
Technical Data Sheet TLE Scalable Series 40 - 150 UL S1
100
120
100
120
98.9
98.9
98.6
98.7
98.3
98.4
62
(higher the temperature, shorter
the storage time of the battery)
/
3000m: -10%
50
80
100
120
47.7
76.3
95.3
114.4 143.0
53.0
84.7
105.9 127.1 158.9
59.1
96.9
118.1 145.4 177.2
12
24
24
36
150
150
98.9
98.7
98.4
150
36