The number of SEM Operation Mode hours per weekday "Monday to Sunday" is displayed in the
operation mode parameter window (ceiling value).
NOTE !
To avoid undesired SEM Operation Mode, verify:
Date and Time.
SEM screen how many hours of SEM Operation Mode have been selected for
each day of the week.
NOTE !
The SEM Operation Mode will become active only if the Load is supplied from the
Inverter.
SEM Operation Mode is only possible if the UPS load exceeds a minimum threshold
(default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI
mode.