Status messages and alarm messages

The NetPro UPS alerts the user with a blinking ! signal on the LCD that the status has changed or that an
alarm situation occurs. The accompanying screen messages appear after the push-buttons $ $ $ $ or # # # # have
been pressed. The blinking ! signal will disappear from the display (see also 3.4.1).
3 kinds of messages can be displayed on the LCD:
- status indications
(3.4.2.1)
- low priority alarms
(3.4.2.2)
- high priority alarms
(3.4.2.3)
Table 1 shows an overview of all messages
Message text
On line
On battery
On bypass
Error
Battery low
Fan error (NetPro 3/4k)
Overload
Output error
High temperature
Input converter error
Charger error (NetPro 2k)
Charger error (NetPro 3/4k)
Temperature
Replace battery
Bypass error
Progr.outlet off (NetPro 3/4k)
Input error
Weak mains
Table 1: NetPro screen messages
OPM_NPE_XXX_2K0_4K0_1GB_V040
indicate the UPS operating mode
indicate abnormal operating situations; the screen message is accompa-
nied by a 1x per 8 secs. sounding buzzer. The buzzer is resettable with the
OK button (19), but only after the default screen is displayed again.
In case of 'weak mains' the yellow LED (16) on the front panel illuminates
and the buzzer remains silent.
indicate situations in which the connected load is at risk as a proper output
voltage of the UPS is no longer guaranteed; immediate action should be
taken. The screen message is accompanied by a red LED 'alarm' and a 1x
per second sounding buzzer. The buzzer is resettable with the OK button
(19).
Status indication
!
!
!
!
7
GE Digital Energy
Kind of message
High priority
Low priority
alarm
!
!
!
!
!
!
!
!
NetPro 2000-4000: user manual 4.0 (GB)
alarm
!
!
!
!
!
!
!
!