40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

STATIC BYPASS
Input configuration
Primary components
Transfer limits
Overload capability (on bypass)
Short circuit capability (on bypass)
eBoost
OPERATING MODE
TM
Input wiring configuration
Output waveform
Transfer time to Inverter
Transfer limits
Steady-state RMS tolerance
Instantaneous voltage distortion
(with respective to Normal Sine wave)
Steady-state frequency tolerance
Instantaneous phase shift
EXTERNAL INTERFACE
Alarm contacts (voltage-free)
Standard
Optional
Communication
Input signals
Diagnostics
5
TLE Series UPS 160/200/225/250 Technical Datasheet
Single input (standard) or dual input (optional)
Fully rated continuous duty static switch
Back feed protection + Semiconductor fuse for clearing fault currents
+/- 10% of nominal output voltage (adjustable)
110% continuous
150% for 1 minute
1000% for 1/2 cycle (non-repetitive)
480VAC, 3-phase, 4 wire + ground
Continuously monitored
<2ms (typical)
+/-20 Vrms (adjustable)
Magnitude
Duration
+/-3 Hz
0.15 radians (8.5 Deg)
6 user defined contacts (form 'C') (1A / 24V DC)
12 user defined contacts (form 'C') (1A / 24V DC)
(23 selectable signals include aux. Inputs 1 & 2)
RS-232 / SNMP / MODBUS
Emergency Power Off (user supplied N.C. contact)
Aux. input 1
* (default = On Generator)
Aux. input 2
* (configurable)
* Status displayed on LCD panel
Internal Waveform Capture. Input and output w/pre and post event data (Field Service Only)
GECriticalPower.com
OR 3 wire + ground
+/-75Vp
500µs (adjustable)