40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

Code
4697
BATTERY OVERTEMPERATURE
4698
BATTERY POWER INSUFFICIENT
4700
4701
POWER SUPPLY BOARD FAILURE
4702
LOSS OF REDUNDANCY
4900
LOAD LOCKED ON INVERTER
4955
OVERTEMPERATURE
LOAD OFF DUE TO EXTENDED
4998
LOAD OFF DUE TO LOW BATT. OR
4999
Modifications reserved
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
Alarm
DC LOW
OVERLOAD
TEMP.
Description
Detection of Battery overtemperature condition.
Only a GE Service Engineer can reset the alarm.
In case of Utility Failure, with the actual Load, the
run time would be below stop operation time
(default 3 minutes).
Battery voltage is at the lowest limit.
Inverter will remain Off until the battery voltage
reaches the value in parameter.
Detection of a failure on the Power Supply Board, in
particular from the DC supply.
Can be enabled or disabled with respective
parameter.
A time of lost redundancy superior than specified in
respective parameter was detected.
The Load is locked on Inverter after 3 Load transfers
within 30 seconds.
After time out (default 30 sec.) Bypass will be free.
An overtemperature condition has been detected on
Inverter.
Elapsed "stop operation" time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
Load Off after time-out of "stop operation" for
overload on Inverter (time depending on the % of
overload).
Load Off after time-out of "stop operation" with
missing Utility due to Battery low voltage or
overtemperature condition.
Page 38/90
User Manual TLE Scalable Series 40 - 150 UL S1