Events (Alarms And Messages); Alarms List - GE 8 Series Operating Manual

Table of Contents

Advertisement

7.3.1 Events (alarms and messages)

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software "GE Data Protection" installed or with the monitoring system "GE Power Diagnostic".
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signalled with the LED alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the acoustical alarm).

7.3.2 Alarms list

Code
Alarms
4000
SETUP VALUES LOST
4001
REGULATION BOARD FAILURE
UPS FAILURE
4004
ON PARALLEL SYSTEM
4006
BUS JA CRC FAILURE
4007
BUS JB CRC FAILURE
4008
BUS JA FAILURE
4009
BUS JB FAILURE
4010
CONNECTIVITY BUS FAILURE
4104
BATTERY FUSES FAILURE
RECTIFIER TRANSFORMER
4106
OVERTEMPERATURE
RECTIFIER MAINS OUT
4110
OF TOLERANCE
4115
LOW BATTERY VOLTAGE
4116
HIGH BATTERY VOLTAGE
4117
BATTERY EARTH FAULT
4118
BATTERY FAULT
4121
HIGH DC RIPPLE
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Parameters are lost and have been replaced with default
values.
A blocked DSP on the Control board causes this alarm, and
consequently the shutdown of rectifier and inverter and the
opening of K3.
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
The parallel communication bus system is subject to high
errors rate on channel JA.
The parallel communication bus system is subject to high
errors rate on channel JB.
There is an interruption in the channel JA of the parallel
communication bus system.
There is an interruption in the channel JB of the parallel
communication bus system.
The connectivity communication bus is faulty or interrupted.
This function, when enabled on input programmable relays
(password required), warns the user about the external
battery fuses failure or MCB opening, signalled by NO free
contact.
The temperature sensor inside the input transformer
winding indicates overtemperature. Only the alarm is given.
The rectifier, when in an Off state, cannot start as long as
this condition persists.
Rectifier input mains is out of tolerance (voltage, frequency
or phase).
The battery has been discharged and reached "stop
operation" time-out (default 3 minutes), and the inverter will
be shut down.
It will restart automatically only when the battery has
recharged enough for a minimum runtime.
Dangerous high UDC-Voltage.
Causes inverter shutdown.
Inverter restarts automatically after battery returns to
normal floating voltage.
A leakage current to earth has been detected on the DC
circuit.
During battery test the voltage falls under the critical level
(depending setting parameters).
Battery test is stopped.
A high ripple is present in the battery voltage.
Meaning
Operating Manual SitePro 10-15-20-30-40 kVA / S8
Page 49/99