Connecting the SAN Volume Controller 2145-4F2 to the 2145 UPS

Connecting the SAN Volume Controller 2145-4F2 node to the 2145 uninterruptible
power supply (2145 UPS) requires that you first review the restrictions that exist
between the two systems.
Each SAN Volume Controller 2145-4F2 of a pair must be connected to a different
2145 UPS. Each 2145 UPS can support up to two SAN Volume Controller
2145-4F2s.
Attention: Do not connect two nodes to the same pair of 2145 UPSs. Both nodes
are lost in the event that a power failure occurs on both of those 2145 UPSs.
Note: You must install 2145 UPSs in pairs. There must be at least two 2145 UPSs
Before you begin this task, refer to the user's cable connection table in the IBM
System Storage SAN Volume Controller: Planning Guide to identify the 2145 UPS to
which this SAN Volume Controller 2145-4F2 is to be connected.
Perform the following steps to connect the SAN Volume Controller 2145-4F2 to the
2145 UPS:
1. At the back of the SAN Volume Controller 2145-4F2, plug a power cable into
72
IBM System Storage SAN Volume Controller: Installation Guide
"Inspecting the SAN Volume Controller for unsafe conditions" on page xii
Use caution when working in any potential safety hazardous situation that is
not covered in the safety checks. If unsafe conditions are present, determine
how serious the hazards are and whether you can continue before you correct
the problem.
"External machine check" on page xiii
Ensure that you perform an external machine check before you install the SAN
Volume Controller.
"Internal machine checks" on page xiii
Ensure that you perform an internal machine check before you install the SAN
Volume Controller.
"Inspecting the UPS for unsafe conditions" on page xviii
Ensure that you take the time to inspect the uninterruptible power supply
(UPS) for unsafe conditions.
Related reference
"SAN Volume Controller controls and indicators" on page 5
All controls and indicators are located on the front panel of the SAN Volume
Controller.
"SAN Volume Controller rear panel indicators" on page 11
The indicators for the SAN Volume Controller are contained on the front and
back panel assembly. The following graphics show the rear panel indicators.
"Controls and indicators for the 2145 UPS-1U" on page 30
All controls for the 2145 uninterruptible power supply-1U (2145 UPS-1U) are
located on the front panel assembly.
per cluster. A cluster can contain no more than eight SAN Volume Controller
2145-4F2s. Also, ensure that each 2145 UPS of a pair is connected to a
separate electrical input power source (if possible) to reduce the chance of
input power failure at both 2145 UPSs.
1
the power connector
. See Figure 50 on page 73.