7. Remove the protective label from the internal battery connector.
Figure 32. Internal battery connector with protective label
8. Connect the internal battery connector.
Note: A small amount of arcing might occur when connecting the batteries.
This is normal and does not damage the unit or present any safety
concerns.
9. Reinstall the front panel.
10. At the back of the 2145 UPS-1U, plug the 2145 UPS-1U main power connector
into the power socket (
standby mode, so all indicators are off.
Note: The 2145 UPS-1U is intended to maintain power on SAN Volume
Controller nodes until data can be saved to the local hard disk drive.
Only SAN Volume Controller nodes can be plugged into the 2145
UPS-1U or the SAN Volume Controller cluster malfunctions.