Omron NT620S Operation Manual page 92

Programmable terminals
Hide thumbs Also See for NT620S:
Table of Contents

Advertisement

Registering the Screen Data
Note
Precautions to be Observed During the Screen Data Transmission
6. When the screen data transmission is completed, the support tool will display
the following screen.
– – – – – Help Message – – – – –
Data successfully transmitted
(Hit any key to continue)
7. Press any key on the support tool to return to the File Selection screen.
8. Pressing the "Abort" touch switch in the Transmit Mode screen of the
NT620S/620C will exit the Transmit Mode and enter the RUN Mode.
Press the "Abort" touch switch on the NT620S/620C when the screen data
transmission is completed. Unless this touch switch is pressed, the screen data
will not be correctly registered. If the "Abort" touch switch is pressed during
transmission, the screen data will not be correctly registered.
If screen data cannot be transmitted from the support tool properly, check wheth-
er communication between the NT620S/620C and support tool (personal com-
puter) is normal.
To check communication with the support tool, use the "Tool Transmit" function in
the maintenance mode of the NT620S/620C. See "Checking the Communica-
tions with the Support Tool" (page 98).
When any of the following or a system error occurs during the screen data trans-
mission, the transmitted screen data will not be registered correctly to the
NT620S/620C. If an error message is displayed in the System Menu and the
Transmit Mode cannot be selected, the screen data memory needs to be initial-
ized.
S The power to the NT620S/620C is interrupted or the NT620S/620C is reset.
S The power to the computer on which the support tool is running is interrupted or
the computer is reset.
S The cable connecting the NT620S/620C to the computer on which the support
tool is running is disconnected or has a broken wire.
S The "No" touch switch on the NT620S/620C screen is pressed to end the trans-
mission during screen data transfer.
S The "ESC" key on the support tool is pressed to end the transmission.
When the power to the NT620S/620C is turned ON or reset, the screen data is
checked. However, if any of the above occurs during the screen data transmis-
sion, the screen may disappear and other unexpected problems may occur.
In the case of such problems, set DIP SW2-1 to ON to initialize the memory.
Section
3-6
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt620c

Table of Contents