Model SK-5208 Fire Control/Communicator Installation and Operation Manual
A.2

Two-Wire Smoke Detectors

The table below lists two-wire smoke detectors that are compatible with the SK-5208 and SK-
5217 zone expander. The table is organized by manufacturer. The columns show the number
of detectors per loop that can be used.
Enhanced
Manufactu
Mode
rer
Compatible
Apollo
Detection
Systems
ESL
A-10
Model Name or Number
(Base model name or number in
parentheses.)
55000-150, 151, 152, 153
55000-250
55000-350
55000-380
55000-225
55000-226
55000-227
55000-325
55000-328
55000-326
55000-327
DS200 (MB200-2W)
DS200HD (MB200-2W)
DS250 (MB2W or MB2WL)
DS250HD (MB2W or MB2WL)
DS250TH (MB2W or MB2WL)
425 (S10)
425C (S10)
425CR (S10)
425CRT (S10)
425CT (S10)
429C (S10A)
429CRT (S11A)
429CST (S11A)
429CT (S10A)
521B
521BXT
609U01-11
609U02-11
611U (601U or 602U)
611UD (601U or 602U)
611UT (601U or 602U)
612U (601U or 602U)
612UD (601U or 602U)
firealarmresources.com
Compatibility ID
Head
Base
55000-150,
45681-200, 220, 230,
151, 152, 153
231, 232
55000-350
45681-200, 220, 230,
231, 232
55000-250
45681-200, 220, 230,
231, 232
55000-380
45681-200, 220, 230,
231, 232
55000-225
45681-255, 256
55000-226
55000-227
45681-200, 220, 230,
55000-325
232, 251, 252
55000-328
55000-326
55000-327
B
A
B
A
B
A
B
A
B
A
N/A
S00
N/A
S00
N/A
S00
N/A
S00
N/A
S00
N/A
S10A
N/A
S11A
N/A
S11A
N/A
S10A
N/A
S10A/S11A
N/A
S10A/S11A
S10
S00
S10
S00/S03
S10
S00/S03
S10
S00/S03
S10
S00/S03
S10
S00/S03
S10
S00/S03
# per Loop
40
40
25
15
15 / loop for
Ion Detectors
15 / loop for
Photoelectric
detectors
24
24
18
18
18
30
30
30
30
30
30
30
30
30
40
40
40
40
40
40
40
40
40