Hitachi L100 Instruction Manual page 74

L100 series
Hide thumbs Also See for L100:
Table of Contents

Advertisement

3–18
Automatic Voltage Regulation (AVR) Function
Func.
Code
A81
AVR function select
A82
AVR voltage select
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
"A" Group: Standard Functions
The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a
relatively constant amplitude during power input fluctuations. This can be useful if the
installation has an erratic power source. However, the inverter cannot boost its motor
output to a voltage higher than the power input voltage. If you enable this feature, be
sure to select the proper voltage class setting for your motor.
"A" Function
Name
Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00 ...AVR enabled
01 ...AVR disabled
02 ...AVR enabled except
during deceleration
200V class inverter settings:
.......200/220/230/240
400V class inverter settings:
.......380/400/415/440/460
Run-
time
Description
Edit
Defaults
DOP,DRW,DOP+
EU/
Func.
Units
Name
US
Code
02
F-03
AVR
MODE
230/
V
F-03
AVR AC
230,
400/
460