Troubleshooting Tips - Hitachi L100 Instruction Manual

L100 series
Hide thumbs Also See for L100:
Table of Contents

Advertisement

Troubleshooting Tips

Symptom/condition
The motor
will not run.
The direction of the motor is
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
The table below lists typical symptoms and the corresponding solution(s).
Is the frequency command source
A01 parameter setting correct?
Is the Run command source A02
parameter setting correct?
Is power being supplied to termi-
nals L1, L2, and L3(N)? If so, the
POWER lamp should be on.
Is there an error code
displayed?
The inverter
outputs U, V, W
are not supply-
Are the signals to the intelligent
ing voltage.
input terminals correct?
Is the Run Command active?
Is the [FW] terminal (or [RV])
connected to P24 (via switch, etc.)
Has the frequency setting for F01
been set greater than zero?
Are the control circuit terminals H,
O, and L connected to the potenti-
ometer?
Is the RS (reset) function or FRS
(free-run stop) function on?
Inverter outputs
Is the motor load too heavy?
U, V, W are
supplying
voltage.
The optional
Are the operational settings
remote operator
between the remote operator and
is used (DR/W)
the inverter unit correct?
Are the connections of output
terminals U/T1, V/T2, and W/T3
correct?
Is the phase sequence of the motor
forward or reverse with respect to
reversed.
U/T1,V/T2, and W/T3?
Are the control terminals [FW] and
[RV] wired correctly?
Is parameter F04 properly set?
Probable Cause
EXX
L100 Inverter
Solution
Make sure the parameter
setting A01 is correct.
Make sure the parameter
setting A02 is correct.
Check terminals L1, L2, and
L3(N), then U/T1, V/T2,
and W/T3.
Turn on the power supply or
check fuses.
Press the Func. key and
determine the error type.
Then clear the error (Reset).
Verify the terminal functions
for C01 - C05 are correct.
Turn on Run Command.
Supply 24V to [FW] or [RV]
terminal, if configured.
Set the parameter for F01 to
a safe, non-zero value.
If the potentiometer is the
frequency setting source,
verify voltage at "O" > 0V.
Turn off the command(s).
Reduce load, and test the
motor independently.
Check switches 1 and 2 on
the optional remote operator
(copy unit).
1
2
3
4
1: Off
ON
2: On
OFF
Make connections according
to the phase sequence of the
motor. In general:
FWD = U-V-W, and
REV=U-W-V.
Use terminal [FW] for
forward, and [RV] is reverse.
Set motor direction in F04.
6–3