L100 inverters, 400V models
Applicable motor size *2 kW
Rated capacity (460V) kVA *10
Rated input voltage
Rated input current (A)
Rated output voltage *3
Rated output current (A)
Braking
Weight
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
Item
004HFE
004HFU
0.4
HP
1/2
1.1
2.0
1.5
Dynamic braking,
approx. % torque,
(short time, stopping
Capacitive feedback type, dynamic braking unit and braking resistor optional,
from 50 / 60 Hz) *5
individually installed
DC braking
kg / lb
1.3/2.9
Footnotes for the preceding tables and the table on the following page:
*1: The protection method conforms to JEM 1030.
*2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). To use other
motors, care must be taken to prevent the rated motor current (50/60 Hz) from exceeding the
rated output current of the inverter.
*3: The output voltage decreases as the main supply voltage decreases (except for use of the
AVR function). In any case, the output voltage cannot exceed the input power supply
voltage.
*4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer about the maximum
allowable rotation speed.
*5: The braking torque via capacitive feedback is the average deceleration torque at the shortest
deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking
torque. And, the average deceleration torque varies with motor loss. This value decreases
when operating beyond 50 Hz. Note that a braking unit is not included in the inverter. If a
large regenerative torque is required, the optional regenerative braking unit should be used.
*6: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10 VDC,
or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not convenient for your
application, contact your Hitachi sales representative.
*7: If operating the inverter in an ambient temperature of 40–50 C, reduce the carrier frequency
to 2.1 kHz, derate the output current by 80%, and remove the top housing cover. Note that
removing the top cover will nullify the NEMA rating for the inverter housing.
*8: The storage temperature refers to the short-term temperature during transport.
*9: Conforms to the test method specified in JIS C0911 (1984). For the model types excluded in
the standard specifications, contact your Hitachi sales representative.
*10:The input voltage of xxLFU is 230V.
400V Class Specifications
007HFE
015HFE
022HFE
007HFU
015HFU
022HFU
0.75
1.5
2.2
1
2
3
1.9
3.0
4.3
3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
3.3
5.0
7.0
3-phase: 380 to 460V (corresponding to input voltage)
2.5
3.8
5.5
100%: 50Hz
50%:
60Hz
Variable operating frequency, time, and braking force
1.7/3.7
1.7/3.7
2.8/6.2
L100 Inverter
030HFE
040HFE
055HFE
040HFU
055HFU
3.0
4.0
5.5
4
5
7.5
6.2
6.8
10.4
10.0
11.0
16.5
7.8
8.6
13
40%:
50Hz,
20%:
20%:
60Hz
20%: 60Hz
2.8/6.2
2.8/6.2
5.5/12.1 5.7/12.5
1–5
075HFE
075HFU
7.5
10
12.7
20.0
16
50Hz

Hide quick links: