Table of Contents

Advertisement

Quick Links

P
lease read this manual carefully before you install and operate an L100 series inverter and observe all of
the instructions given in there. This manual may also serve as a reference guide und therefore should always
be kept at hand.
Symbols used
There are several safety instructions in this manual which are marked with a special hazard alert symbol
(flash or exclamation mark in the center of a triangle). Additionally, either the word CAUTION or
WARNING is added following the triangle with the exclamation mark.
This symbol means hazardous high voltage. It is used to call your attention to items or operations
that could be dangerous to your or other persons life. Please read the safety message carefully and
follow all the instructions given.
This symbol is used to call your attention to situations which are potentially dangerous to persons.
Please read the safety message carefully and follow all the instructions given.
The safety messages given following this symbol are further divided into two categories:
WARNING
CAUTION
HAZARDOUS HIGH VOLTAGE
Motor control equipment or electronic controllers are connected to hazardous line
voltages. When servicing drives and electronic controllers there migh exist exposed
components with cases ore protrusions at or above line potential. Extreme care should
be taken to protect against shock.
For these reasons, the following safety guidelines should be observed:
Stand on an insulating pad and make it a habit to use only one hand when checking
components. Disconnect power before checking controllers or performing
maintenance. Be sure that equipment is grounded properly. Wear safety glasses
whenever working on an electronic controller or rotating electrical equipment.
WARNING This equipment should be installed, adjusted and serviced only by qualified electrical
maintenace personell familiar with the construction and operation of the equipment
and the hazards involved. Failure to observe this precaution could result in bodily
injury.
WARNING The user is responsible that all driven machinery, drive train mechanism not supplied
by Hitachi, Ltd., and process line material are capable of safe operation at an applied
frequency of 150% of the maximum selected frequency range to the AC motor. Failure
to do so can result in destruction of equipment and injury to personnell should a single
point failure occur.
WARNING HAZARD OF ELECTRICAL SHOCK. DISCONNECT INCOMING POWER
BEFORE WORKING ON THIS CONTROL.
WARNING SEPERATE MOTOR OVERLOAD AND OVERCURRENT PROTECTION
DEVICES ARE REQUIRED TO BE PROVIDED IN ACCORDANCE WITH THE
SAFETY CODES REQUIRED BY JURISDICTIONAL AUTHORITIES.
CAUTION
These instructions should be read and clearly understood before working on L100
series equipment.
CAUTION
Proper grounds, disconnecting devices (e.g. fuses) and other safety devices and their
location are the responsibility of the user and are not provided by Hitachi, Ltd.
CAUTION
DANGEROUS VOLTAGE EXISTS UNTIL THE POWER LIGHT ON THE
DIGITAL OPERATOR IS OFF.
CAUTION
Rotating shafts and electrical potentials above ground level can be hazardous.
Therefore it is strongly recommended that all electrical work conform to the national
This message indicates a situation which may lead to serious injury or even
death if the instruction is not observed.
This message indicates a situation which may lead to minor or moderate
injury, or damage of product.

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi L100-004 HFE

  • Page 1 WARNING The user is responsible that all driven machinery, drive train mechanism not supplied by Hitachi, Ltd., and process line material are capable of safe operation at an applied frequency of 150% of the maximum selected frequency range to the AC motor. Failure to do so can result in destruction of equipment and injury to personnell should a single point failure occur.
  • Page 2 electrical codes and local regulations. Installation, maintenance and alignment should be performed by qualified personnell only. Factory recommended test procedures included in this instruction manual should be followed. Always disconnect electrical power before working on the unit. WARNING a) Any motor used must be of suitable rating. b) Motors may have hazardous moving parts so that suitable protection must be provided in order to avoid injury.
  • Page 3 L100-007 NFE 1 ~ 220V -10% thru 240V +5% FPF-L100N/2x4.0A L100-011 NFE FPF-L100N/2x10A L100-015 NFE FPF-L100N/2x10A L100-022 NFE FPF-L100N/2x10A L100-004 HFE FPF-L100H/3x3.8A L100-007 HFE FPF-L100H/3x3.8A L100-015 HFE FPF-L100H/3x3.8A L100-022 HFE FPF-L100H/3x8.6A 3 ~ 380 V -10% thru 460V +10% L100-030 HFE FPF-L100H/3x8.6A...
  • Page 4 The amount of line-conducted interference also increases as motor cable length increases. Adherence to the interference limits for line-conducted interference is guaranteed on following way: • If maximum motor cable length is 10 m at maximum elementary frequency: Class „B“. •...
  • Page 5 Technical specifications and dimensions of L100 foot print filter: at 40°C ambient temperature Current 1.5 x I N for 10min Overload HITACHI POWER 55.0 50 / 60 Hz Frequency STOP RESET FUNC. Steel, surface refined Material L 1 0 0...
  • Page 6 Revision history table: Revision contents Date of issue Manual no. Correction: Specification for RESET terminal September, 1997 NB541XC Correction: Initial data for C 31 and C 32 Addition of 5,5kW and 7,5kW models July, 1998 NB541XD Addition of insulating resistance test Addition of the magnetizing current setting via b 32 Revision and expansion of the section "Notes on EMC (electro magnetical compatibility)"...
  • Page 7: Table Of Contents

    C O N T E N T S CHAPTER 1 – SAFETY PRECAUTIONS ........................1-1 NSTALLATION ..........................1-1 IRING ...................... 1-2 ONTROL AND OPERATION ....................1-3 AINTENANCE AND INSPECTION ..........................1-3 THERS CHAPTER 2 – INSPECTION UPON UNPACKING ............... 2-1 CHAPTER 3 –...
  • Page 8 CHAPTER 8 – USING THE DIGITAL OPERATOR ................. 8-1 HE DIGITAL OPERATOR CONTROL PANEL ................... 8-1 PERATING PROCEDURE EXAMPLE ......................8-2 IGITAL OPERATOR KEYS VERVIEW OF PARAMETER SETTINGS Display functions ........................ 8-3 Basic functions........................8-4 Extended functions of group A....................8-4 Extended functions of group B....................
  • Page 9: Chapter 1 - Safety Precautions

    Chapter 1 – Safety precautions Chapter 1 – Safety precautions Installation The following safety precautions are to be observed when installing the frequency inverter: CAUTION Be sure to install the inverter on flame resistant material such as metal. Otherwise, there is a danger of fire. CAUTION Be shure not to place anything inflammable in the vicinity.
  • Page 10: Control And Operation

    Chapter 1 – Safety precautions cause unintentional triggering of earth leakage circuit breakers. Because of the rectifier on the input side of the inverter there is the possibility to stall the switch-off function through amounts of DC current. For these reasons, the following items should be observed: Only pulse current sensitive earth leakage circuit breakers which have a short term delay and a higher trigger current (500mA) should be used.
  • Page 11: Maintenance And Inspection

    Chapter 1 – Safety precautions Maintenance and inspection WARNING Before carrying out maintenance and inspection wait for at least five minutes after having turned off the input power supply. Otherwise, there is a danger of electric shock. WARNING When removing connectors (e.g. from fans and printed circuit boards) never pull the attached wires.
  • Page 12 Chapter 1 – Safety precautions well apart from the inverter. It is also effective to shield the whole inverter structure (refer to figure below, left part). Grounded piping or shielded wire Noise Inverter EMI filter L1(L1) T1(U) Motor Motor T2(V) L3(N) T3(W) Noise...
  • Page 13: Chapter 2 - Inspection Upon Unpacking

    Mfg No. 761T1234570001 Date: 9706 Manufacturing number, date (example: June 1997) Hitachi, Ltd. Made in Japan NE16452-9 In the illustration below, the contents of the model designation used for L100 series inverters is explained: L100 Version number ( _ , 1, 2 ...)
  • Page 14: Chapter 3 - Appearance And Names Of Parts

    Chapter 3 – Appearance and names of parts Chapter 3 – Appearance and names of parts Digital operator Digital operator Key cover (can be opened) (can be opened) ( Note 1 ) ( Note 2 ) (Note 2) Key cover (Note 1) Screw Casing...
  • Page 15 Chapter 3 – Appearance and names of parts digital operator Alarm Screw (can be opened) terminals ( Note 2 ) (Note 2) Control terminals Key cover Rear cover Serial grounding (opened) Mains circuit interface terminal (PE) Casing terminals Cooling fin Alarm Digital operator terminals...
  • Page 16: Chapter 4 - Installation

    The minimum clearances to the surrounding walls shown in the figure are only meant for reference. A more compact installation (back to back) may well be possible and should be discussed with Hitachi. Please always leave enough room for the key cover to be opened without problems in order to connect wires to the control terminals.
  • Page 17: Chapter 5 - Wiring

    Chapter 5 – Wiring Chapter 5 – Wiring CAUTION Fasten the screws with the specified fastening torque so that they will not loosen unintentionally. Check all terminals for loose screws. Otherwise there is a danger of fire. CAUTION Remarks for using earth leakage circuit breakers in the mains supply Frequency inverters with CE-filters (RFI-filter) and screened motor cables have a higher leakage current against earth.
  • Page 18: Wiring The Control Terminals

    Chapter 5 – Wiring Thermal relay L100 4) The leads from the power supply must be connected to the mains circuit terminals as follows: Connect single phase power supply (50/60Hz) to terminals L1, L3/N. Connect three phase power supply (50/60Hz) to terminals L1, L2, L3/N. 5) Don´t remove the short bar between the terminals +1 and +.
  • Page 19: General Remarks

    Chapter 5 – Wiring General remarks When connecting cables, the following items must be observed: When changing the power supply of the motor between the inverter and commercial power line, be sure to install mechanically interlocked switches (S1 and S2) as shown in the figure below: Earth leakage circuit breakers Power...
  • Page 20 Chapter 5 – Wiring Mains circuit power cable (L1, L2, L3(N), U, V, W, +1, +, - ) 90 ° -angle Signal line (H, O, OI, L, FM, 1, 2, 3, 4, 5, 11, 12, CM2, P24) Separate by 10cm or more Do not short circuit the terminals P24 and L, H, OI, or FM by mistake, because this may cause a malfunction.
  • Page 21: Wiring Equipment And Options

    Chapter 5 – Wiring Wiring equipment and options CAUTION Provide the wiring equipment in accordance with the safety codes required by jurisdictional authorities. If specified in standards or laws and regulations, follow their istructions. In the following table some guidelines for choosing an appropriate wire gauge are presented: Cable specifications Motor...
  • Page 22: Terminals

    Chapter 5 – Wiring Part description Function This part is used when the unbalance ratio is 3% or more and the power supply is 500kVA or more, and AC reactor there are rapid changes in the power supply. This part also improves the power factor.
  • Page 23 Chapter 5 – Wiring The following table shows the location and dimensions of all terminals: 007NF~022NF 055LF, 075LF 037LF 002NF, 004NF 055LF, 075HF Location of control terminals 004HF~040HF Width Width Width L FM Terminal type Screw Screw Screw Location of Power terminal M3.5 alarm terminals...
  • Page 24 Chapter 5 – Wiring Terminal Purpose Initial setting Remarks categorie Reference for frequency command input 10V DC; max. 10mA Set value 0-10V; Frequency Voltage frequency command Input impedance 10k Ohm command input Set value 4-20mA; Current frequency command Input impedance 250 Ohm Common for frequency command input The digital outputs can be user Frequency arrival signal...
  • Page 25: Chapter 6 - General Operation Notes

    Chapter 6 – General operation notes Chapter 6 – General operation notes Before starting operation Prior to the test run, the following items should be checked: 1) Make sure that the power lines (input power supply terminals L1(L1), L2, and L3(N)) and output terminals (U(T1), V(T2) und W(T3)) are connected correctly.
  • Page 26 Chapter 6 – General operation notes In order to test the inverter, follow the procedure described below: 1) Turn on power supply to the inverter. The power LED on the digital operator will light up. 2) Set function A 02 to 02. 3) Set function A 01 to 00.
  • Page 27: Chapter 7 - Control Circuit Terminal Functions

    Chapter 7 – Control circuit terminal functions Chapter 7 – Control circuit terminal functions Overview Terminal Terminal function Description symbol Frequency Forward run Forward run (00) (Start/Stop) Reverse run Reverse run Input FW closed: Motor starts with forward running direction. (01) (Start/Stop) Input FW open: Motor decelerates from forward running.
  • Page 28 Chapter 7 – Control circuit terminal functions Terminal Terminal function Description symbol 24V DC common for Common terminal for the intelligent digital inputs digital inputs Set value configured Set value configured Set value configured 10V reference voltage using potentiometer: using voltage input: using current input: for analog set value (using potentiometer)
  • Page 29: Fm Terminal

    Chapter 7 – Control circuit terminal functions FM terminal Terminal function This terminal is used for connecting an analog voltmeter or a digital frequency meter and thus to monitor and display output frequency. Alternatively, motor current can be monitored instead (when output current is selected the FM terminal can only supply an analog signal).
  • Page 30: Terminals 1 - 5 (Programmable Digital Inputs)

    Chapter 7 – Control circuit terminal functions Terminals 1 - 5 (programmable digital inputs) General notes Several functions can be assigned to the terminals 1 through 5. Depending on the application these terminals can be configured to be forward (FW) or reverse run (RV) inputs, multistage speed setting inputs (CF1-CF4), reset input (RS), and so on.
  • Page 31: Fw: Start/Stop Forward Run

    Chapter 7 – Control circuit terminal functions FW: Start/stop forward run Terminal function When a digital input configured as FW is activated the motor starts running in the forward direction. When it is deactivated the motor stops. 1 P24 The motor stops if both the FW and the RV inputs are activated. Configuration A 02 C 01 –...
  • Page 32: Cf1 - Cf4: Multistage Speed Settings

    Chapter 7 – Control circuit terminal functions CF1 – CF4: Multistage speed settings Terminal function Using the digital inputs configured as CF1 – CF4 one of up to 16 freely selectable frequencies (including the set value) can be sent to the motor depending on which terminals are activated or deactivated (refer to table below).
  • Page 33: At: Analog Set Value Using Current 4-20Ma

    Chapter 7 – Control circuit terminal functions AT: Analog set value using current 4-20mA Terminal function When a digital input configured as AT is activated then the frequency set value will be represented by the current (4-20mA) fed into the OI terminal. When the AT input is not active then the frequency set value will be represented by the voltage (0-10V) present at the O terminal.
  • Page 34: Frs: Free Run Stop

    Chapter 7 – Control circuit terminal functions FRS: Free run stop Terminal function When a digital input configured as FRS is activated, then the inverter stops output and the motor enters the free run state (e.g. emergency stop). When the FRS input is deactivated again, the inverter either synchronizes to the free running motor´s current speed or it restarts with an output of 0 Hz depending on inverter configuration.
  • Page 35: Usp: Prevention Of Restart Upon Power Recovery

    Chapter 7 – Control circuit terminal functions USP: Prevention of restart upon power recovery Terminal function When a digital input configured as USP is activated, then the inverter won´t restart when power to the inverter recovers and a running command (activated FW or RV input) is being active at the same time. The trip E 13 is output in this case which dissapears when the trip is acknowledged by pressing the RESET key, activating the RS input, or releasing the running signal again.
  • Page 36: Rs: Reset

    Chapter 7 – Control circuit terminal functions RS: Reset Terminal function A trip can be acknowledged using a sequence of activation and subsequent deactivation of an input configured as RS. 12ms min. 1 P24 Terminal RS Alarm output (relay) approx. 30ms Configuration C 01 –...
  • Page 37: Jg: Jogging Run

    Chapter 7 – Control circuit terminal functions JG: Jogging run Terminal function When a digital input configured as JG is activated, then the motor can be driven in jogging mode. This is useful for example when preparing a machine in manual operation mode. In this case a low frequency (without the usual acceleration ramp) is sent to the motor when the FW or RV input is activated along with the JG input.
  • Page 38: Ptc: Thermistor Input

    Chapter 7 – Control circuit terminal functions PTC: Thermistor input Terminal function When the programmable digital input 5 is configured as PTC, motor temperature can be monitored when a thermistor with a positive temperature coefficient is connected to terminals 5 and L. When the thermistor resistance rises to above 3000 Ohms (+/-10%), operation of the motor is stopped and the trip is E 35 displayed.
  • Page 39: Terminals 11, 12 (Programmable Digital Outputs)

    Chapter 7 – Control circuit terminal functions Terminals 11, 12 (programmable digital outputs) General notes The programmable digital outputs 11 and 12 are transistor outputs with open collector (refer to the figure below) which can be used to connect relays. Various functions can be assigned to these two outputs according to user demands.
  • Page 40: Fa1, Fa2: Frequency Arrival Signals

    Chapter 7 – Control circuit terminal functions FA1, FA2: Frequency arrival signals Terminal function A digital output configured as FA1 will be activated as soon as the set frequency has been reached. A digital output configured as FA2 will stay activated at frequencies above those set under C 42 and C 43. In order to provide for a certain amount of hysteresis during switching on and off, the FA1 and FA2 signals are activated 0.5Hz before the current frequency reaches the set value or the frequency set under C 42, respectively.
  • Page 41: Ol: Overload Signal

    Chapter 7 – Control circuit terminal functions OL: Overload signal Terminal function A digital output configured as OL is activated as soon as a user definable overload limit is exceeded. The OL output remains active as long as the motor current lies above this limit. Current 12 11 27V max.
  • Page 42: Al: Alarm Signal

    Chapter 7 – Control circuit terminal functions AL: Alarm signal Terminal function A digital output configured as AL is activated when an alarm condition exists and the inverter trips. 27V max. 50mA max. Configuration C 21 C 22 Program one of the digital outputs 11 or 12 as AL output by entering the parameter 05 under C 21 or C 22. Remarks •...
  • Page 43 Chapter 7 – Control circuit terminal functions Terminals AL0, AL1, AL2 (alarm relay) Terminal function When a trip occurs the alarm relay (double throw switch) is activated. The user can choose which terminal is to function as normally open and which as normally closed contact. A trip message is displayed on the digital operator's display.
  • Page 44: Chapter 8 - Using The Digital Operator

    Hz or A Lamp Hz or A lamp is on PRG Lamp during display of POWER HITACHI This lamp is on frequency or current. while a parameter is being set. Potentiometer This potentiometer sets...
  • Page 45 Chapter 8 – Using the digital operator Digital operator keys 58.1 After the data is changed, press the STR key to save data 58.0 F 02 F 02 [UP key, DOWN key] ... These FUNC keys change parameter values. FUNC Pressing the FUNC key leaves data unchanged 57.9...
  • Page 46: Overview Of Parameter Settings

    Chapter 8 – Using the digital operator Overview of parameter settings In the following chapters all parameters that can be set using the digital operator are described and listed in tables. Starting with chapter “Basic functions” the column “Standard setting” lists the factory preconfigured parameter settings.
  • Page 47: Basic Functions

    Chapter 8 – Using the digital operator Basic functions Standard Function Display Function description / parameter setting range setting Setting range 0.5Hz–360Hz (resolution +/-0.1Hz). The frequency can be set using the following methods: Using F 01 and A 20: Enter the parameter 02 under A 01. Using the potentiometer on the digital operator.
  • Page 48 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Analog set value adjustment The external frequency set value can be individually adjusted A 12 using functions A 11 to A 16. A configurable voltage or A 15 = 00 current set value range can be assigned to a configurable frequency range.
  • Page 49 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Voltage/frequency characteristics, boost The boost causes a higher voltage (and consequently higher 100% torque) in the lower frequency range. The manual boost raises voltage in the frequency range from start frequency (standard setting of 0.5Hz) to half of the base frequency (25Hz at a A 42=50%...
  • Page 50 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Upper/lower limiter, jump frequency Upper fre- quency limit The frequency range set by b 82 (start frequency) and A 04 A 61 (maximum frequency) can be further limited using functions A 61 and Lower fre- A 62 (refer to the upper figure on the left).
  • Page 51 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting (Continued from previous page) control is not used, in this case it is really the set value that gets adjusted. So when the PID control is activated, the functions A 11 through A 14 do not adjust the set value but the actual value instead).
  • Page 52 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Automatic Voltage Regulation (AVR) The AVR function causes motor voltage stabilization when DC voltage is fluctuating (e.g. due to an instable mains supply or a dropping or excessive DC voltage as a result of too short acceleration or deceleration times) and thus ensures a high torque (especially during acceleration).
  • Page 53: Extended Functions Of Group B

    Chapter 8 – Using the digital operator Extended functions of group B Most of the functions of group B serve safety purposes or are used to protect the inverter from damages. Standard Function Display Function description / parameter setting range setting Automatic restart after inverter trip WARNING On occurance of a trip condition this function causes an automatic inverter...
  • Page 54 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Overload restriction The overload restriction function is used to limit motor current. motor Overload During acceleration, the rise in frequency is stopped as soon as the output limit current exceeds the configured overload limit.
  • Page 55 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Other functions The analog signal output on terminal FM (representing frequency set Analog meter value or output current) can be adjusted using this function. However, b 81 adjustment adjustment of the pulse signal (digital frequency set value) is not...
  • Page 56 Chapter 8 – Using the digital operator Extended functions of group C The functions of group C are used for configuring the programmable digital inputs and outputs. Standard Function Display Function description / parameter setting range setting Programmable digital inputs Digital inputs 1, 2, 3, 4, and 5 can be assigned 15 different input functions.
  • Page 57 Chapter 8 – Using the digital operator Standard Function Display Function description / parameter setting range setting Programmable digital outputs Digital outputs can be assigned one of 6 different signalling functions. Both outputs may also be assigned to the same function. The oututs can be programmed either as normally closed contacts or as normally open contacts. One of the following signalling functions can be assigned: 00: RUN signal (signal active during motor run) 01: FA1 signal (frequency arrival)
  • Page 58: Chapter 9 - Messages

    Chapter 9 – Messages Chapter 9 – Messages Trip messages L100 series inverters will trip on overcurrent, overvoltage and undervoltage to protect the inverter.The output is shut down and the motor runs free. This condition is held until the trip state is reset using the RESET key or the RS input.
  • Page 59: Other Messages

    Chapter 9 – Messages Other messages Cause Display The inverter is currently in standby mode There is an active reset signal. The mains power supply has been switched off. The waiting time prior to automatic inverter restart is coming to an end (refer to functions b 01 and b 03). The factory standard settings have been selected and the inverter currently is in its initializing phase (refer to functions b 84 and b 85).
  • Page 60: Chapter 10 - Trouble Shooting

    Chapter 10 – Trouble shooting Chapter 10 – Trouble shooting Error Condition Possible cause Remedy Does a voltage exist at the terminals L1, N (NFE models) or L1, L2 and L3 (HFE Check terminals L1, L2, L3 (U, V, W). models)? If this is the case, is the power Switch on the power supply afterwards.
  • Page 61 Chapter 10 – Trouble shooting Error Condition Possible cause Remedy Choose an inverter and motor of a higher rating. Are the motor load fluctuations too great? The motor run Reduce load fluctuations to a minimum. is unstable Avoid critical frequencies by using jump Are there motor resonating frequencies? frequencies (A 63 –...
  • Page 62: Chapter 11 - Technical Specifications

    Chapter 11 – Technical specifications Chapter 11 – Technical specifications Inverter L 1 0 0 (200V series) Protective structure (Note 1) IP20 Overvoltage category Maximum motor size (4P) 0.55 0.75 in kW (Note 2) 230V 12.7 Maximum capacity in kVA 240V 13.3 Input supply phase...
  • Page 63 Chapter 11 – Technical specifications Inverter L 1 0 0 (400V series) Protective structure (Note 1) IP20 Overvoltage category Maximum motor size (4P) 0.75 in kW (Note 2) Maximum capacity 460V 10.3 12.7 in kVA Input supply phase 004 ~ 075HF: 3 phase Rated input voltage 380VAC –10% ~ 460VAC +10% 50/60Hz +/-5%...
  • Page 64 Notes on technical specifications: Note 1: Protective structure is based upon EN60529 Note 2: The applicable motor is a Hitachi standard four-pole motor. When using another motor, make sure that the rated motor current does not exceed the rated inverter current.
  • Page 65 Chapter 11 – Technical specifications External dimensions and terminal positions of L100 series inverters Legend: A Control terminals B Alarm terminals C Main terminals D Grounding terminals (All dimensions are in millimeters) 11-4...
  • Page 66 Chapter 11 – Technical specifications L100- 055 LFU/HFE/HFU 075 LFU/HFE/HFU L100- 022 NFE/NFU 022 HFE/HFU 030 HFE 037 LFU 040 HFE/HFU Legend: A Control terminals B Alarm terminals C Main terminals D Grounding terminals (All dimensions are in millimeters) 11-5...
  • Page 67: Set Value Supplied By External Potentiometer

    Chapter 12 – Wiring examples Chapter 12 – Wiring examples Set value supplied by external potentiometer Connection diagram Potentiometer Frequency monitor 1 ... 2kOhm (0..10V, 1mA) Configuration of parameters Configurable Function Description parameters A 01 Set value input using control terminals A 02 Running command using terminals FW/RV F 02...
  • Page 68: Inverter Operation Using Analog Set Value

    Chapter 12 – Wiring examples Inverter operation using analog set value Connection diagram Motor thermistor (PTC) Set value (4...20mA) Configuration of parameters Configurable Function Description parameters A 01 Set value input using control terminals A 02 Running command using terminals FW/RV F 02 Acceleration time in s F 03...
  • Page 69: Inverter Operation Using Fixed Set Values

    Chapter 12 – Wiring examples Inverter operation using fixed set values Connection diagram +24V Configuration of parameters Configurable Function Description parameters A 01 Set value input using control terminals A 02 Running command using terminals FW/RV F 02 Acceleration time in s F 03 Deceleration time in s C 01...
  • Page 70: Chapter 13 - The Optional Remote Operators

    Chapter 13 – The optional remote operators Chapter 13 – The optional remote operators Connection of the remote operator Before the optional remote operators DOP, DRW, or OPE-J can be connected the power supply to the inverter has to be switched off. Then the cable must be plugged into the inverter as shown in the figure. Now the power supply can be switched on again.
  • Page 71 Chapter 13 – The optional remote operators The monitor mode ) marked column indicates whether parameters can The following table describes the display contents. The be changed during inverter operation (Y) or not (N). Standard Parameter Refer Function Display contens Notes setting range...
  • Page 72 Chapter 13 – The optional remote operators The function mode When the remote operator DOP or the copy unit DRW is connected to an L100 series inverter the parameters listed in the following table can be configured. Funct. Standard setting Parameter Refer Function...
  • Page 73 Chapter 13 – The optional remote operators Funct. Standard setting Parameter Refer Function Display range Rated Rated 50~150% of Overload limit current OLOAD LVL 20.63A b 22 current current rated current *1,25 *1,25 F-24 OLOAD CONST 01.0 b 23 Deceleration rate 0.1~30 OFF, ON, OLOAD MODE...
  • Page 74 Chapter 13 – The optional remote operators Funct. Standard setting Parameter Refer Function Display range CARRIER 12.0kHz b 83 F-36 Carrier frequency 5.0kHz 5.0kHz 0.5~16 F-37 Function of FM terminal MONITOR A-F, A, D-F C 23 INIT SEL b 85 National version EUR, USA F-38...
  • Page 75: Protective Functions

    Chapter 13 – The optional remote operators Protective functions Cause Description Message During con- When the output of the inverter is OC. Drive stant speed short circuited, the motor is locked, or Overcurrent Deceleration OC. Decel a heavy load is suddenly applied, and protection the inverter output current exceeds a Acceleration...
  • Page 76: Dimensions Of Accessories

    Chapter 13 – The optional remote operators Dimensions of accessories Remote operator DOP-0A Copy unit DRW-0A2 Cutout for panel mounting Cutout for panel mounting Remote operator Cable for L100 / J100 / J300 Boss for ex- OPE-J tensive cable 18,5 12,5 13,7 Cutout for 25mm...
  • Page 77: Using The Copy Unit

    Chapter 13 – The optional remote operators Using the copy unit The following table lists the steps that are necessary to copy the configuration (i.e. the parameters) to three other inverters B, C, and D: Action Key(s) Result Read out data The data stored in inverter A must be read READ...
  • Page 78: Chapter 14 - Service And Warranty

    Chapter 14 – Service and warranty Chapter 14 – Service and warranty Should you encounter any problems with your Hitachi inverter, please consult your local sales representative. Please provide the following information about your inverter: 1) The exact inverter model name (this information can be found on the inverter nameplate next to Model:) 2) Date of purchase 3) Serial number (this information can be found on the inverter nameplate next to MFG.
  • Page 79: Appendix A - Printed Form For User Defined Parameter Settings

    Appendix A – Printed form for user defined parameter settings Appendix A – Printed form for user defined parameter settings L100 series inverters provide many functions whose parameters can be set by the user. It is recommended that the parameters that have been set by the user be recorded to speed the investigation and repair in the event of a failure.
  • Page 80 Appendix A – Printed form for user defined parameter settings Standard Display Function S e t v a l u e setting A 38 Jogging frequency A 39 Jogging stop mode 00-Free run 01-Deceleration using decel. ramp 02-Deceleration using DC brake A 41 Boost selection method 00-Manual 01-Automatic...
  • Page 81 Appendix A – Printed form for user defined parameter settings Standard Display Function S e t v a l u e setting b 01 Restart mode 00-Trip message 01-0Hz start / start frequ. start 02-Synchronization to motor speed + acceleration 03-Synchronization to motor speed + deceleration b 02 Allowable undervoltage failure time...
  • Page 82 Appendix A – Printed form for user defined parameter settings Standard Display Function S e t v a l u e setting C 01 Function of digital input 1 00: FW (start/stop forward run) 01: RV (start/stop reverse run) 02: CF1 (1. multispeed) 03: CF2 (2.
  • Page 83: Appendix B - Printed Form For User Defined Parameter Settings (Remote Operator

    Appendix B – Printed form for user defined parameter settings (remote operator) Appendix B – Printed form for user defined parameter settings (remote operator) L100 series inverters provide many functions whose parameters can be set by the user. It is recommended that the parameters that have been set by the user be recorded to speed the investigation and repair in the event of a failure.
  • Page 84 Appendix B – Printed form for user defined parameter settings (remote operator) Standard Function (monitor mode) Display S e t v a l u e setting Remote OPE-J display contents PANEL Status of input and output terminals TERM LLL LLLLL Display only, no params can be entered ERR1 ERR1...
  • Page 85 Appendix B – Printed form for user defined parameter settings (remote operator) Standard setting Func. Function (Function mode) Display S e t v a l u e F-00 Base frequency F-BASE 050Hz 50Hz 60Hz F-01 Maximum frequency F-MAX 050Hz 50Hz 60Hz F-02 Start frequency...
  • Page 86 Appendix B – Printed form for user defined parameter settings (remote operator) Standard setting Func. Function (Function mode) Display S e t v a l u e LIMIT L 000.0Hz Frequency lower limit F-26 Frequency upper limit LIMIT H 000.0Hz 1.
  • Page 87: Appendix C - Initializing The Inverter

    Appendix C – Initializing the inverter Appendix C – Initializing the inverter If it becomes necessary to initialize the inverter (i.e. reset the inverter to the factory standard settings or just clearing the trip history register) you will have to do the following: First refer to the nameplate to find out if the inverter is a European version (L100-####FE) or an American version (L100-####FU).

Table of Contents