3–20
Func.
Code
A96
Dec1 to Dec2
frequency transition
point
A97
Acceleration curve
selection
A98
Deceleration curve
setting
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
"A" Group: Standard Functions
"A" Function
Name
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve
Set the characteristic curve of
Acc1 and Acc2, two options:
00 ...linear
01 ...S-curve
NOTE: For A95 and A96, if you set a very rapid Acc1 or Dec1 time (less than 1.0
second), the inverter may not be able to change rates to Acc2 or Dec2 before reaching
the target frequency. In that case, the inverter decreases the rate of Acc1 or Dec1 in order
to achieve the second ramp to the target frequency.
Run-
time
Description
Edit
Defaults
DOP,DRW,DOP+
EU/
Func.
Units
Name
US
Code
0.0
Hz
F-07
DEC
CHFr
00
F-06
ACC
LINE
00
F-07
DEC
LINE