Overload Advance Notice Signal - Hitachi L100 Instruction Manual

L100 series
Hide thumbs Also See for L100:
Table of Contents

Advertisement

4–20

Overload Advance Notice Signal

Option
Code
03
Valid for outputs:
Required settings:
Notes:
The default value is 100%. To change the level
from the default, set C41 (overload level).
The accuracy of this function is the same as the
function of the output current monitor on the [FM]
terminal (see page 4–25).
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
Using Intelligent Output Terminals
When the output current exceeds a preset
value, the [OL] terminal signal turns on.
The parameter C41 sets the overload
threshold. The overload detection circuit
operates during powered motor operation
and during regenerative braking. The
output circuits use open-collector
transistors, and are active low.
Terminal
Function Name
Symbol
OL
Overload advance
notice signal
11, 12, AL0 – AL2
C41
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter's output transistor.
Current
C41
set
value
C41
[OL]
Signal
threshold
Output
Description
State
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold
for the overload signal
Example:
Inverter output
terminal circuit
H
O
OI
See I/O specs on page 4–5.
threshold
power running
regeneration
threshold
ON
ON
time
OL
FM
CM2
L
12
11
+
RY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents