When programming the multi-speed settings, be
sure to press the Store key each time and then set
the next multi-speed setting. Note that when the
key is not pressed, no data will be set.
When a multi-speed setting more than 50Hz(60Hz)
is to be set, it is necessary to program the maximum
frequency A04 high enough to allow that speed.
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
Using Intelligent Input Terminals
Terminal
Function Name
Symbol
C01, C02, C03, C04, C05
F01, A20 to A35
While using the multi-speed capability, you can monitor the current frequency with
monitor function D01 during each segment of a multi-speed operation.
There are two ways to program the speeds into the registers A20 to A35:
1. Standard keypad programming:
a. Select each parameter A20 to A35.
b. Press the
key to view the parameter value.
FUNC.
c. Use the
and
1
d. Use the
key to save the data to memory.
STR
2. Programming using the CF switches. Set the speed by following these steps:
a. Turn the Run command off (Stop Mode).
b. Turn each switch on and set it to Multi-speed n. Display the data section of F01.
c. Set an optional output frequency by pressing the
d. Press the
key once to store the set frequency. When this occurs, F01 indicates
STR
the output frequency of Multi-speed n.
e. Press the
key once to confirm that the indication is the same as the set
FUNC.
frequency.
f. When you repeat operations in 2. a) to 2. e), the frequency of Multi-speed n can
be set. It can be set also by parameters A20 to A35 in the first procedure 1. a) to
1. d).
Input
State
Example:
See I/O specs on page 4–5.
2
keys to edit the value.
Description
(MSB)
(LSB)
CF4 CF3
CF2 CF1
P24
L
5
4
3
2
1
and
keys.
2
1