2–20
Keys, Modes, and Parameters
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
Using the Front Panel Keypad
• Function Key - This key is used to navigate
through the lists of parameters and functions
for setting and monitoring parameter values.
• Up/Down (
,
2
) Keys - Use these keys
1
alternately to move up or down the lists of
parameter and functions shown in the display,
and increment/decrement values.
• Store (
) Key - When the unit is in
STR
Program Mode and the operator has edited a
parameter value, press the Store key to write
the new value to the EEPROM.
Purpose of the keypad is to provide a way to change modes and parameters. The term
function applies to both monitoring modes and parameters. These are all accessible
through function codes, which are primarily 3-character codes. The various functions are
separated into related groups identifiable by the left-most character, as the table shows.
Function
Type (Category) of Function
Group
"D"
Monitoring functions
"F"
Basic profile parameters
"A"
Standard functions
"B"
Fine tuning functions
"C"
Intelligent terminal functions
"E"
Error codes
For example, function "A 04" is the base frequency setting for the motor, typically 50 Hz
or 60 Hz. To edit the parameter, the inverter must be in Program Mode (PGM LED will
be On). You use the front panel keys to first select the function code "A 04." After
displaying the value for "A 04," use the Up/Down (
NOTE: The inverter 7-segment display shows lower case "b" and "d", which means the
same as the upper case letters "B" and "D" used in this manual (for uniformity "A to F").
The inverter automatically switches into Monitor
Mode when you access "D" group functions. It
switches into Program Mode when you access any
other group, because they all have editable param-
eters. Error codes use the "E" group, and appear
automatically when a fault event occurs. Refer to
page 6–5 for error code details.
HITACHI
RUN
5 0
0
PRG
STOP
STOP
STOP
STOP
RUN
RESET
MIN
2
FUNC.
1
Function
Up/Down
key
keys
PGM LED
Mode to Access
Indicator
Monitor
Program
Program
Program
Program
or
) keys to edit the value.
2
1
MONITOR
"D" Group
POWER
Hz
A
MAX
STR
Store
key
PROGRAM
"A" Group
"B" Group
"C" Group
"F" Group