Connection Example - Panasonic FPS Series User Manual

Table of Contents

Advertisement

FPΣ User's Manual

8.7.6 Connection Example

The following example demonstrates how the PLC can be connected to two other PLCs using
a PLC link connection. In the example shown here, link relays are used. When X1 of station
number 1 turns to TRUE, Y1 of station number 2 turns to TRUE. When X2 of station number 1
turns to TRUE, Y1 of station number 3 turns to TRUE.
X1: TRUE
X2: TRUE
FP-X
#1
#
Station number of PLC
Link relay L0 turns to TRUE
1
Link relay L1 turns to TRUE
2
System register settings
For PLC Link, the communication format and baud rate settings are fixed:
No.
Name
413
COM port 1 - communication format
415
COM port 1 - baud rate
NOTE
FPG-COM4: The baud rate of 115200bit/s must be set with switch SW1-2 on the
cassette. See "DIP Switch Setting on FPG-COM4" on page 162.
Set communication mode and station numbers using the system registers:
Settings for FP-X (station number 1)
No.
Name
410
COM port 1 - station number
412
COM port 1 - communication mode
Y0: TRUE
FPΣ
RS485
#2
Y0: TRUE
FP2/FP2SH
#3
Set value
Data length:
8 bits
Parity:
Odd
Stop bit:
1 bit
End code:
CR
Start code:
No STX
115200bit/s
Set value
1
PLC Link
8.7 PLC Link