Overview - Panasonic FPS Series User Manual

Table of Contents

Advertisement

High-Speed Counter and Pulse Output

7.1 Overview

Three built-in hardware extensions allow the FPΣ to be used for positioning control and
measurement: high-speed counting, pulse output, and PWM (pulse-width modulation) output.
High-speed counter function
The high-speed counter function counts external inputs such as those from sensors or
encoders. When the count reaches the target value, this function turns the desired output to
TRUE or to FALSE.
PLC
1
Encoder
2
Motor
3
Roller
4
Inverter
5
Cutter
6
Tape, lead wire
7
Pulse output function
By connecting a commercially available motor driver to the PLC, positioning control can be
performed with the pulse output function. Using special instructions, trapezoidal control, home
return, or JOG operation is possible. Linear and circular movements by simultaneous control
of two axes using interpolation functions are possible.
A
Y0
Y1
Y3
Y4
PLC
A
Motor driver
B
Stepping motor/servo motor
C
100
a
b
c
Encoder output is input to the high-speed counter
a
Start/stop signal
b
Cutter blade control signal
c
B
C
CW pulse output
1
CCW pulse output
2
FPΣ User's Manual